Bringing transparency to federal inspections
Tag No.: K0140
The facility failed to ensure the oxygen supply system and all components were in accordance with the requirements for a Type I Gas System. NFPA 99, Chapter 4. Observation determined the medical gas system alarm panel, with an audible and visual alarm, was not installed at an attended location.
Failure to ensure oxygen supply systems comply with NFPA 99 increases the risk of death or injury due to fire.The deficiency affected the entire facility.