Tag No.: K0077

Based on observation the facility failed to provide adequate medical gas system.

The inspector observed, while accompanied by the Plant Operations and Maintenance personnel during the hours of the inspection from 11:15 pm to 1:15 pm on 01/07/2014 that there were the following issues:


A.) Based on observation the facility failed to provide individual chains for the medical gases bottles. This does not comply with the following NFPA code. " Cylinders in service and in storage shall be individually secured and located to prevent falling or being knocked over. " - NFPA 99, 1999: 4-3.1.1.1.

No Description Available

Tag No.: K0106

Based on observation the facility failed to provide adequate receptacles and battery powered lighting units.

The inspector observed, while accompanied by the Plant Operations and Maintenance personnel during the hours of the inspection from 11:15 pm to 1:15 pm on 01/07/2014 that there were the following issues.

(1). There was a missing battery powered lighting units and a missing receptacle powered from life safety branch at a) the generator set location and b) the essential automatic transfer switch location.

" The emergency generator location shall have task illumination, battery charger for emergency battery powered lighting unit(s), and selected receptacles at the generator set location and essential automatic transfer switch location " - NFPA 99, 1999: 3-4.2.2.2.(b)5.