HospitalInspections.org

Bringing transparency to federal inspections

810 FAIRGROVE CHURCH RD

HICKORY, NC 28602

No Description Available

Tag No.: K0018

Based on observation, on March 11, 2014 at approximately 1:45pm onward, the door to critical care waiting room is less than forty inches in width. Door is approximately thirty six inches - located in Critical Care South Unit.

42 CFR 482.41(a)

No Description Available

Tag No.: K0020

Based on observation, on March 12, 2014 at approximately 2:00amm onward, vertical chases are incomplete due to the following:

1. unsealed penetrations in chase located in pharmacy area.

2. fire curtain obstructed to tray conveyor chase - located on lower level pharmacy by tray cart.

3. lack of guardrail protection at each floor level of tray conveyor chase.

42 CFR 482.41(a)

No Description Available

Tag No.: K0029

Based on observation, on March 12, 2014 at approximately 2:00am onward, hazardous areas are incomplete due to the following:

1. lack of sprinkler(s) for volunteer storage room - room exceeds 100 square feet in area. room is located on first floor.
2) The trash room door located in the kitchen was not self closing.
3) The dry storage room door was held open preventing the door from closing.
4) The corridor door to sterile processing (L057) lower level did not have positive latching.
5) The door to material management storage room was not a rated door.

42 CFR 482.41(a)

No Description Available

Tag No.: K0032

Based on observation, on March 12, 2014 at approximately 2:00am onward, exits are not assured due to the following:

1. incomplete electromagnetic locking arrangement on exit access door from PACU to OR corridor - system installed is not equipped with motion sensor as required for access controlled egress door.

42 CFR 482.41(a)

No Description Available

Tag No.: K0034

Based on observation on 3/13/14 at approximately 6:00 AM onward the following deficiencies were noted:
1) The stairwell corridor door located next to the mechanical room did not close and latch and was dragging on the floor preventing the door from closing.

42 CFR 483.70

No Description Available

Tag No.: K0038

Based on observation, on March 11, 2014 at approximately 1:45pm onward, the exit access is not assured due to the following:

1. the use of momentary contact switch beside doors equipped with special locking arrangements - located near room 3136.

2. the use of momentary contact switch beside door equipped with special locking arrangements - located at smoke barrier between connecting breezeway and existing main hospital.

4. the use of deadbolt locks located above 48 inches from finished floors on doors to the following rooms:

a. room 3134

b. room 3136

42 CFR 482.41

No Description Available

Tag No.: K0046

Based on observation, on March 12, 2014 at approximately 2:00am onward, there is no emergency lighting for rear exit discharge of MRI Unit.

42 CFR 482.41(a)


26594

Based on observation, on March 11, 2014 at approximately 2:30 PM onward, the following deficiencies were noted:
1) By observation exit discharge illumination was observed as noncompliant: specific findings include that the facility could not verify that all exit discharge lighting was connected to emergency power. Lighting must be arranged to provide light from the exit discharge leading to the public way . The walking surfaces within the exit discharge shall be illuminated to values of at least 1 ft-candle measured at the floor. Failure of any single lighting unit does not result in an illumination level of less than 0.2 ft-candles in any designated area. NFPA 101 7.8.1.1, 7.8.1.3, and 7.8.1.4.
2) Exit discharge illumination was not provide for at the Same Day Surgery stairwell door.
3) Exit discharge Illumination was not provided for at the ambulance parking bay rear corridor exit.


42 CFR 482.41(a)

No Description Available

Tag No.: K0047

Based on observation, on March 12, 2014 at approximately 2:00am onward, exit and directional signs are incomplete due to the following:

1. lack of exit sign at intersecting corridors - located on first floor area leading to Oncology Unit.

42 CFR 482.41(a)

2. lack of exit directional sign for ninety degree corridor area leading from MRI to Day Surgery.

42 CFR 482.41(a)


26594

Based on observation, on March 11, 2014 at approximately 2:30 PM onward, the following deficiencies were noted:
1) Exit and directional signage was not provided in the corridor located outside plant operations located on lower level to the stairwell located outside sterile processing.

42 CFR 482.41(a)

No Description Available

Tag No.: K0051

Based on observation, on March 13, 2014 at approximately 5:00am onward, the facility fire alarm system is incomplete due to the following:

1. lack of labeling of normal power circuit breaker serving the main fire alarm control panel - circuit and panelboard must be identified on fire alarm control panel.

2. lack of smoke detector located in vicinity of main fire alarm control panel.

42 CFR 482.41(a)

No Description Available

Tag No.: K0056

Based on observation, on March 12, 2014 at approximately 2:00 AM onward, sprinkler coverage was incomplete due to the following:
1) In the material management storage room (Lower Level) the lower duct works was blocking the overhead sprinkler head.

2) The facility utilizes Special Locking devices on required egress/exit doors - The facility is basically 100% sprinklered with the following exceptions:

By observation sprinkler heads were missing in the following areas;
a) Morgue Shower room
b) Rear Kitchen walk-in refrigeration units
c) Electrical closet in kitchen next to cookline.
d) Mechanical room, kitchen area next to rear entrance.

42 CFR 482.41(a)

No Description Available

Tag No.: K0062

Based on observation, on March 12, 2014 at approximately 2:00am onward, maintenance of the automatic sprinkler system is incomplete due to the following:

1. heat sensitive element of pendent sprinkler is covered by lint and debris - located in ED waiting area.


42 CFR 482.41(a)


13743

Based on observation, on March 11, 2014 at approximately 1:45pm onward, the seventh floor laundry chute was not verified to have a sprinkler installed at the top of the chute


26594

Based on observation, on March 12, 2014 at approximately 2:00am onward, sprinkler tamper alarm incomplete due to the following:
1) The sprinkler tamper alarm located on 6th floor north stairwell was equipped with an unapproved tamper alarm.

42 CFR 482.41(a)

No Description Available

Tag No.: K0067

Based on observation, on March 11, 2014 at approximately 2:30pm onward, the mechanical systems are noncompliant due to the following:

1. nonlisted mechanical duct used at ceiling level in main dining room - the material doesn't meet UL duct classifications required in health care facilities.

42 CFR 482.41(a)

No Description Available

Tag No.: K0069

Based on observation, on March 11, 2014 at approximately 2:30 PM onward, the following deficiencies were noted:
1) On the cook lines there is an oven and other equipment cooking equipment located on the cook line that were not properly located under the hood.

42 CFR 482.41(a)

No Description Available

Tag No.: K0070

Based on observation, on March 12, 2014 at approximately 2:00am onward, there are exposed element, high temperature portable space heaters used in the following areas:

1. office beside fastrack area on first floor.

2. pharmacy office

3. VP office located in administration area.

42 CFR 482.41(a)

No Description Available

Tag No.: K0072

Based on observation, on March 12, 2014 at approximately 2:00am onward, the means of egress clearance is incomplete due to the following:

1. impediments by mechanical equipment in floor area to MRI - located beside anesthesia on call room.

2. impediments in means of egress - corridor area near TrueBeam room.

42 CFR 482.41(a)

No Description Available

Tag No.: K0076

Based on observation, on March 11, 2014 at approximately 1:45pm onward, the fifth floor respiratory department had nitrous oxide cylinders that were not individually chained.

No Description Available

Tag No.: K0104

Based on observation, on March 11, 2014 at approximately 1:45pm onward, there are no smoke damper installed in the ductwork that penetrate the smoke wall above the cross corridor doors that lead into the "C" section suite.

No Description Available

Tag No.: K0106

Based on observation, on March 11, 2014 at approximately 1:45pm onward, the essential electrical system is incomplete due to the following:

1. LS Branch panelboard ELW3 contains a smoke guard system not permitted on the Life Safety Branch of the essential electrical system - located in Pavilion electrical room on third floor.

42 CFR 482.41

No Description Available

Tag No.: K0147

Based on observation, on March 12, 2014 at approximately 2:00am onward, the facility electrical system is incomplete due to the following:

1. lack of weatherproof receptacle with ground-fault interrupter protection for outlets serving Lipo Truck - located beside MRI exit.

42 CFR 482.41(a)

No Description Available

Tag No.: K0160

Based on observation, on March 11, 2014 at approximately 1:45pm onward, the document review noted that the NCDOL inspection report on 3/4/2014 had incomplete items including: cleaning oil from the car top and stop the leak at the drive machine.

Means of Egress - General

Tag No.: K0211

Based on observation, on March 11, 2014 at approximately 1:45pm onward, the fifth floor small nurses station chart area near room 522 had an alcohol based hand rub dispenser installed over an ignition source the light switch in that area.