111 CENTRAL AVENUE

NEWARK, NJ 07102

No Description Available

Tag No.: K0038

Based on observation, it was determined that, the facility failed to have a readily accessible exit.

Findings include:

1. On 2/13/12 at 10:50 AM, in the presence of Staff #1, at the 3rd floor access of the 'D' building #2 exit stair, the stair tread was found cracked and supported with a wood 4x4.

No Description Available

Tag No.: K0052

Based on observation, it was determined that, the facility failed to maintain an operating fire alarm system.

Findings include:

1. On 2/13/12 at 11:10 AM, in the presence of Staff #1, in the morgue, two smoke detectors were found covered with construction caps, disabling them.

Means of Egress - General

Tag No.: K0211

Based on observation, it was determined that, the facility failed to ensure Alcohol Based Hand Rub dispensers (ABHR) are not installed above ignition sources.

Findings include:

1. On 10/31/11 at 10:10 AM, in the presence of Staff #1, in the endoscopy clean utility room, an ABHR was observed installed above an electrical switch.