2360 ROCKMART HIGHWAY

CEDARTOWN, GA 30125

Corridors - Construction of Walls

Tag No.: K0362

During the survey conducted 12/05/2016 to determine compliance with the requirements of 42 CFR Part 482, Subpart C with Federal regulations, the following deficiencies were cited.
A service window located in the wall next to corridor access door for the pharmacy is not code compliant:
The window will not prevent the passage of smoke, glass is not sealed in frame, at the bottom of the window is a pass threw hole (2 inch X 11 inch).
NFPA 101 (2012 edition) 19.3.6.2, 19.3.6.2.7

Gas Equipment - Cylinder and Container Storag

Tag No.: K0923

During the survey conducted 12/05/2016 to determine compliance with the requirements of 42 CFR Part 482, Subpart C with Federal regulations, the following deficiencies were cited.
12- H size cylinders located in bulk O2 tank area, are not protected from weather and direct sun light.
NFPA-99-2012 edition 11.3.1, 11.3.2, 11.3.3, 11.3.4, 11.6.5