Smoke Detection

Tag No.: K0347

Sensitivity testing of smoke detectors is to be completed for all smoke detectors during the first year in service, and the alternate year following. After the second required calibration test, if the detector has remained within its listed and marked sensitivity range, the length of time between calibration tests may be extended, not to exceed five years. 19.3.4.5, 9.6.2.10.1.1, NFPA 72 14.4.5.3

The facility failed to ensure smoke detectors were maintained, inspected and tested in accordance with NFPA 72, National Fire Alarm and Signaling Code.

Review of the fire alarm test results indicated the smoke detection system did not have sensitivity testing at frequencies in compliance with the minimum requirements of NFPA 72.

Records indicated two (2) smoke detectors in the facility were replaced on 05/10/2021 and there were no records available to show sensitivity testing had been completed during the first year of service.

Failure to test the smoke detection system in accordance with NFPA 72 increases the risk of death or injury due to fire.

This deficiency affected two (2) of numerous smoke detectors in the facility.