Tag No.: K0025
Based on surveyor observations, the facility failed to maintain smoke barriers in accordance with NFPA 101 Section 8.3.
Findings are as follows:
1. Observation on 11/16/2011 of the one-hour/smoke barrier wall located on the ground floor, adjacent to the exterior courtyard, revealed an approximate 6 " X 5 " penetration of the wall located above the double smoke compartment doors (above the ceiling tiles).
Tag No.: K0025
Based on surveyor observations, the facility failed to maintain smoke barriers in accordance with NFPA 101 Section 8.3.
Findings are as follows:
1. Observation on 11/16/2011 of the two-hour building separation/smoke barrier wall located on the ground floor entrance to the " Waiting Area " , revealed (4) 2 " diameter penetrations of the wall located above the double smoke compartment doors (above the ceiling tiles).
2. Observation on 11/16/2011 of the two-hour building separation/smoke barrier wall located on the ground floor entrance to the " Borda " building (in corridor outside of the PACU), revealed a 6 " diameter penetration of the wall located above the double smoke compartment doors (above the ceiling tiles).
Tag No.: K0025
Based on surveyor observations, the facility failed to maintain the smoke barriers in accordance with NFPA 101 Section 8.3.
Findings are as follows:
1. Observation on 11/16/2011 of the two-hour building separation/smoke barrier wall located on the ground floor entrance and the corridor to the " Waiting Area " (located in the Surgical Pavilion Building), revealed a 5 " diameter penetration of the wall located above the double smoke compartment doors (above the ceiling tiles) and a 12 " diameter penetration of the corridor wall (above the ceiling tiles).
Tag No.: K0025
Based on surveyor observations, the facility failed to maintain the smoke barriers in accordance with NFPA 101 Section 8.3.
Findings are as follows:
1. Observation on 11/16/2011 of the two-hour building separation/smoke barrier wall located on the ground floor entrance to the " Read " building (located in the corridor separating the " Read " building and the Sturges building), revealed a 4 " diameter penetration of the wall located above the double smoke compartment doors (above the ceiling tiles).
Tag No.: K0056
Based on surveyors ' observations, it was determined that the facility failed to provide protection throughout by an approved, supervised automatic sprinkler system in accordance with NFPA 13 Section 5-5.6.
NFPA 101 Section 19.3.5.3 requires the provision of complete sprinkler coverage for all portions of the building.
1. Observation on 11/16/11 at 10:00AM, in the presence of the Director of Facilities Management Services, of the environmental services closet, located on the ground floor of the East Addition building, revealed no sprinkler protection.
Tag No.: K0056
Based on surveyors ' observations, it was determined that the facility has failed to provide protection throughout by an approved, supervised automatic sprinkler system in accordance with NFPA 13 Section 5-5.6.
NFPA 101 Section 19.3.5.3 requires the provision of complete sprinkler coverage for all portions of the building.
Findings are as follows:
1. Observation on 11/16/11 at 10:30AM, in the presence of the Director of Facilities Management Services, revealed the " 1969 " room / old radiology room (approximately 200 square feet) in the Borda building, lacked sprinkler protection.
Tag No.: K0025
Based on surveyor observations, the facility failed to maintain smoke barriers in accordance with NFPA 101 Section 8.3.
Findings are as follows:
1. Observation on 11/16/2011 of the one-hour/smoke barrier wall located on the ground floor, adjacent to the exterior courtyard, revealed an approximate 6 " X 5 " penetration of the wall located above the double smoke compartment doors (above the ceiling tiles).
Tag No.: K0025
Based on surveyor observations, the facility failed to maintain smoke barriers in accordance with NFPA 101 Section 8.3.
Findings are as follows:
1. Observation on 11/16/2011 of the two-hour building separation/smoke barrier wall located on the ground floor entrance to the " Waiting Area " , revealed (4) 2 " diameter penetrations of the wall located above the double smoke compartment doors (above the ceiling tiles).
2. Observation on 11/16/2011 of the two-hour building separation/smoke barrier wall located on the ground floor entrance to the " Borda " building (in corridor outside of the PACU), revealed a 6 " diameter penetration of the wall located above the double smoke compartment doors (above the ceiling tiles).
Tag No.: K0025
Based on surveyor observations, the facility failed to maintain the smoke barriers in accordance with NFPA 101 Section 8.3.
Findings are as follows:
1. Observation on 11/16/2011 of the two-hour building separation/smoke barrier wall located on the ground floor entrance and the corridor to the " Waiting Area " (located in the Surgical Pavilion Building), revealed a 5 " diameter penetration of the wall located above the double smoke compartment doors (above the ceiling tiles) and a 12 " diameter penetration of the corridor wall (above the ceiling tiles).
Tag No.: K0025
Based on surveyor observations, the facility failed to maintain the smoke barriers in accordance with NFPA 101 Section 8.3.
Findings are as follows:
1. Observation on 11/16/2011 of the two-hour building separation/smoke barrier wall located on the ground floor entrance to the " Read " building (located in the corridor separating the " Read " building and the Sturges building), revealed a 4 " diameter penetration of the wall located above the double smoke compartment doors (above the ceiling tiles).
Tag No.: K0056
Based on surveyors ' observations, it was determined that the facility failed to provide protection throughout by an approved, supervised automatic sprinkler system in accordance with NFPA 13 Section 5-5.6.
NFPA 101 Section 19.3.5.3 requires the provision of complete sprinkler coverage for all portions of the building.
1. Observation on 11/16/11 at 10:00AM, in the presence of the Director of Facilities Management Services, of the environmental services closet, located on the ground floor of the East Addition building, revealed no sprinkler protection.
Tag No.: K0056
Based on surveyors ' observations, it was determined that the facility has failed to provide protection throughout by an approved, supervised automatic sprinkler system in accordance with NFPA 13 Section 5-5.6.
NFPA 101 Section 19.3.5.3 requires the provision of complete sprinkler coverage for all portions of the building.
Findings are as follows:
1. Observation on 11/16/11 at 10:30AM, in the presence of the Director of Facilities Management Services, revealed the " 1969 " room / old radiology room (approximately 200 square feet) in the Borda building, lacked sprinkler protection.