Tag No.: K0025
Based on surveyor observations, the facility failed to maintain smoke barriers in accordance with NFPA 101 Section 8.3.
Findings are as follows:
1. Observation on 11/16/2011 of the one-hour/smoke barrier wall located on the ground floor, adjacent to the exterior courtyard, revealed an approximate 6 " X 5 " penetration of the wall located above the double smoke compartment doors (above the ceiling tiles).
Tag No.: K0056
Based on surveyors ' observations, it was determined that the facility failed to provide protection throughout by an approved, supervised automatic sprinkler system in accordance with NFPA 13 Section 5-5.6.
NFPA 101 Section 19.3.5.3 requires the provision of complete sprinkler coverage for all portions of the building.
1. Observation on 11/16/11 at 10:00AM, in the presence of the Director of Facilities Management Services, of the environmental services closet, located on the ground floor of the East Addition building, revealed no sprinkler protection.