HospitalInspections.org

Bringing transparency to federal inspections

3349 S HIGHWAY 181

KENEDY, TX 78119

No Description Available

Tag No.: K0018

Facility failed to maintain doors in accordance with the 2000 edition of the Life Safety Code, NFPA 101. Findings included the following:

Surveyor observed between 10 and 11 am on 11/13/13, that two exit doors to cafeteria and one exit door to Emergency Department had deadbolt locks in addition to door latch. This is not in accordance with NFPA 101: 7.2.1.5.4 Doors shall be operable with not more than one releasing operation.