HospitalInspections.org

Bringing transparency to federal inspections

220 5TH AVE W

TURTLE LAKE, ND 58575

No Description Available

Tag No.: K0020

The facility failed to provide a one-hour fire resistance rated stair enclosure.

Observation determined the walls of the east stair enclosure stopped at the membrane ceiling and were not extended to the roof deck.

Failure to provide one-hour fire resistance rated vertical openings increases the risk of death or injury due to fire.

This deficiency affected one (1) of three (3) vertical shafts in the building.