Tag No.: K0011
Based on observation the facility failed to ensure 2 hour fire barrier protection seperating the doctor's clinic business occupancy and the health occupancy. Findings:
On 11/12/15 at 2:56 p.m., on inspection of the business occupancy doctor's office clinic on the 3rd floor it was observed there was no 2 hour fire barrier seperating it from the hospital.
At 2:56 p.m., the Director of Physical Services & Safety acknowledged the doctor's office clinic had no fire barrier seperation from the hosptial health occupancy.
Tag No.: K0018
Based on observation it was determined the faclity failed to ensure all doors protecting corridor openings were provided with a means suitable for keeping the door closed. Findings:
On 11/13/15 at 12:04 p.m., the housekeeping closet across from operating room #4 did not have self-closing hardware.
At 12:04 p.m., the Director of Physical Sevices & Safety acknowledged the door without self-closing hardware.
Tag No.: K0025
Based on observation it was determined the facility failed to ensure all smoke barriers were free of penetrations. Findings:
On 11/12/15 at 4:02 p.m., the 3rd floor smoke barrier near the double doors leading to the elevator was observed to have 2 penetrations.
At 4:02 p.m., the Director of Physical Services & Safety acknowledged the penetrations.
On 11/13/15 at 11:49 a.m., the 2nd floor smoke barrier next to housekeeping had 1 penetration. The IT closet on the 2nd floor had 2 penetrations.
At 11:49 a.m., the Director of Physical Services & Safety acknowledged the penetrations.
Tag No.: K0029
Based on observation it was determined the facility failed to ensure hazardous areas were free from penetrations. Findings:
On 11/12/15 at 3:01 p.m., the air handeling unit room #3 was observed to have 2 penetrations.
The Director of Physical Plant & Safety acknowledged the 2 penetrations.