HospitalInspections.org

Bringing transparency to federal inspections

800 KIRNWOOD DRIVE

DE SOTO, TX 75115

Building Services - Other

Tag No.: K0500

Based on observations made during the survey of the facility between the hours of 8:30 am and 12:30 pm, while accompanied by the hospital's CEO, COO, and the Plant Ops Manager it was observed that the facility failed to provide the required filter change log for the pre-filter beds and final filter beds for all AHUs.

Health Care Facilities Code - Other

Tag No.: K0900

Based on observations made during the survey of the facility between the hours of 9:00 am and 1:00 pm, while accompanied by the hospital's CEO, COO, and the Plant Ops Manager it was observed that the facility failed to show the surveyor the required "duct detectors" for 8 AHUs. The dampers were there, and they appeared to be controlled by "something". However, we were not able to locate the duct detectors which normally are required to initiate emergency dampering of the supply and return air ducts.