Bringing transparency to federal inspections
Tag No.: K0025
Based upon observations & discussions there are open or compromised penetrations above the Fire Doors in the Corridors which will allow the passage of smoke & flames from one smoke compartment to another.
Findings include that November 12, 2013 between the hours of 08:30 hours and 16:30 hours, accompanied by the Facilities Director of Support Operations, the following items were noted: Observed open or compromised penetrations in the walls above the Fire Doors that separate the elevator Lobby and the Nurses Stations in the North & South wing on the 3rd & 4th floors; open or compromised penetrations in the walls in the various IT closets and Electrical rooms on the 3rd, 4th and 5th floors. This finding has the potential to affect 60% of the occupants.
The Facilities Director of Support Operations confirmed these findings.
Findings include that November 14, 2013 between the hours of 13:00 hours and 18:00 hours, accompanied by the Facilities Director of Support Operations, the following items were noted: Observed open or compromised penetrations in the walls above the Fire Doors that separate the elevator Lobby and the Nurses Stations in the North & South wing on the 2nd floor; open or compromised penetrations in the walls in the various IT closets and Electrical rooms on the 2nd & 1st floors and in the Materials Management Storage room on the 1st floor. This finding has the potential to affect 40% of the occupants.
.The Facilities Director of Support Operations confirmed these findings.
Tag No.: K0056
Based upon observations, the sprinkler system installation and maintenance accessibility was not in accordance with NFPA 13.
Findings include that November 12, 2013 between the hours of 08:30 hours and 16:30 hours, accompanied by the Facilities Director of Support Operations, the following item was noted: Observed missing sprinkler head coverage under duct work in the mechanical rooms on the 5th floor North and South Wings This finding has the potential to affect 60% of the occupants.
The Facilities Director of Support Operations confirmed these findings.
Findings include that November 14, 2013 between the hours of 13:00 hours and 18:00 hours, accompanied by the Facilities Director of Support Operations, the following items were noted: Observed missing sprinkler head coverage under duct work in the mechanical room of the C U P building near the overhead door by the Fire Pump; missing sprinkler heads in some closets on the 2nd floor in the Family Maternity Center. This finding has the potential to affect 40% of the occupants.
The Facilities Director of Support Operations confirmed these findings.
Tag No.: K0025
Based upon observations & discussions there are open or compromised penetrations above the Fire Doors in the Corridors which will allow the passage of smoke & flames from one smoke compartment to another.
Findings include that November 12, 2013 between the hours of 08:30 hours and 16:30 hours, accompanied by the Facilities Director of Support Operations, the following items were noted: Observed open or compromised penetrations in the walls above the Fire Doors that separate the elevator Lobby and the Nurses Stations in the North & South wing on the 3rd & 4th floors; open or compromised penetrations in the walls in the various IT closets and Electrical rooms on the 3rd, 4th and 5th floors. This finding has the potential to affect 60% of the occupants.
The Facilities Director of Support Operations confirmed these findings.
Findings include that November 14, 2013 between the hours of 13:00 hours and 18:00 hours, accompanied by the Facilities Director of Support Operations, the following items were noted: Observed open or compromised penetrations in the walls above the Fire Doors that separate the elevator Lobby and the Nurses Stations in the North & South wing on the 2nd floor; open or compromised penetrations in the walls in the various IT closets and Electrical rooms on the 2nd & 1st floors and in the Materials Management Storage room on the 1st floor. This finding has the potential to affect 40% of the occupants.
.The Facilities Director of Support Operations confirmed these findings.
Tag No.: K0056
Based upon observations, the sprinkler system installation and maintenance accessibility was not in accordance with NFPA 13.
Findings include that November 12, 2013 between the hours of 08:30 hours and 16:30 hours, accompanied by the Facilities Director of Support Operations, the following item was noted: Observed missing sprinkler head coverage under duct work in the mechanical rooms on the 5th floor North and South Wings This finding has the potential to affect 60% of the occupants.
The Facilities Director of Support Operations confirmed these findings.
Findings include that November 14, 2013 between the hours of 13:00 hours and 18:00 hours, accompanied by the Facilities Director of Support Operations, the following items were noted: Observed missing sprinkler head coverage under duct work in the mechanical room of the C U P building near the overhead door by the Fire Pump; missing sprinkler heads in some closets on the 2nd floor in the Family Maternity Center. This finding has the potential to affect 40% of the occupants.
The Facilities Director of Support Operations confirmed these findings.