Tag No.: K0012

Based on observations, the facility failed to assure that the building is of a conforming construction type. Section 19.1.6.2 requires buildings 3-stories in height to be of at least Type I (443) or Type I (332) or if fully sprinklered of Type II (222).

THE FINDINGS INCLUDE:

- The building is classified as fully sprinklered 3-story Type III (211) construction type.

This was acknowledged by staff during the record review process.

NOTE: This item meets the FSES and does not require corrective action.