Tag No.: K0232
Based on observation, the facility failed to ensure that one corridor of the hospital is of adequate width.
Per observation on 8/20/18, accompanied by the Maintenance Director, the Operating Room Service corridor has a desk that has been placed, restricting the corridor to less than 5 feet in width.
Tag No.: K0291
Based on observation, the facility failed to ensure that emergency lighting is functional in one stairway of the hospital.
Per observation on 8/20/18, accompanied by the Maintenance Director, the stair emergency light was non-functional when tested in the D Stairway, second floor.