Tag No.: K0056

Based on observation, on June 2, 2010 at approximately 5:00am onward, there is no sprinkler system coverage in the following areas:

a. manager's closet - located in PACU/ICU.

b. shower stall in men's dressing room - OR Suite.

This tag waived untill 06/30/2011.

No Description Available

Tag No.: K0067

Based on observation, on June 2, 2010 at approximately 5:00am onward, the following mechanical system components are incomplete:

a. lack of emergency shutdown switch at a supervised station - air handling unit serving operating rooms 1 - 4.


This tag waived untill 06/30/2010.