Tag No.: K0011
The facility failed to ensure complete one-hour fire rated wall assemblies between the 1970 Kidney Dialysis building and the business occupancy located in the 1917 building.
Observation determined a duct penetrating the occupancy separation wall had no fire damper.
Tag No.: K0025
The facility failed to provide smoke barriers with at least one-half hour fire resistance rating at one (1) of two (2) locations.
Observation determined the lack of smoke dampers in two (2) ducts in the 5th floor smoke barrier in the 1960 building.
Note: Verification that the smoke barrier walls extended beyond the plaster ceilings to the roof deck could not be completed due to the integrity of the roof/ceiling assemblies.