Tag No.: K0012

Based on observation, on April 25, 2011 at approximately 1:00pm onward:

1. Room # A468, there were penetrations in rated walls that were not properly sealed to maintain the required fire rating of the walls.

No Description Available

Tag No.: K0018

Based on observation, on April 25, 2011 at approximately 1:00pm onward:

1. 8th Floor, North Tower,- Hemo, Corridor door with self closing device held open with Electro-Magnetic device , did not close upon activation of Fire Alarm as required.

No Description Available

Tag No.: K0020

Based on observation, on April 25, 2011 at approximately 1:00pm onward:

1. The fire door to the eight floor diverter shaft 125 is not self-closing and latching.

No Description Available

Tag No.: K0025

Based on observation, on April 27, 2011 at approximately 5:30am onward:

1. There is a hole in the smoke barrier wall above doors 904A.

No Description Available

Tag No.: K0027

Based on observation, on April 25, 2011 at approximately 1:00pm onward:

1. 4 th Floor - Cross Corridor smoke doors ( # 077B) and (# A457) did not close for smoke tight seal when tested.

No Description Available

Tag No.: K0029

Based on observation, on April 26, 2011 at approximately 7:30 am onward,

1. There are holes in the door to housekeeping room M055 - the door equipped with a hasp that prevents exiting from inside the room.

2. Electrical rooms R-701 & 702 - 2-hr rated walls - There was no fire damper in Exhaust duct thru walls.

No Description Available

Tag No.: K0032

Based on observation, on April 26, 2011 at approximately 7:30am onward,

1. The special locking arrangements for selected doors are noncompliant based upon the following:

a. lack of complete installation in accordance with required building codes - locks at doors 40075C and CCU (7th floor) are not provided with a master release on/off switch at a supervised nurse's station.

2. 6th Floor , Stairwell #61, Exit door equipped with Mag- locks did not release with activation of Fire Alarm, the door did release with over ride switch at door. This must be corrected immediately.

No Description Available

Tag No.: K0033

Based on observation, on April 26, 2011 at approximately 7:30am onward,

1. There is approximately a half inch gap between the meeting edge of fire doors RT01 - the astragal provided is not sufficient to maintain required fire rating.

No Description Available

Tag No.: K0038

Based on observation, on April 26, 2011 at approximately 7:30am onward,

1. The exit access doors require greater than a thirty pound force to set the doors in motion - doors from Chinese garden.

No Description Available

Tag No.: K0040

Based on observation, on April 26, 2011 at approximately 7:30am onward,

1. The horizontal sliding door to room R419 is used as an exit access door - the doors to similar rooms are not located within a suite of rooms.

No Description Available

Tag No.: K0045

Based on observation Monday , 4/25/2011 at approximately 1:00 PM onward :

1. 9th Floor : There was no lighting on Emergency Circuit ( LS Branch) for family waiting room # 90064

2. There was not exit discharge lighting in the exit discharge path from the first floor Reynolds to West & Watlington. (1st floor Reynolds)

No Description Available

Tag No.: K0046

Based on observation, on April 25, 2011 at approximately 1:00pm onward,

1. There is no lighting identified on the Life Safety Branch of the essential electrical system in the following areas:

a. central corridor near the dialysis coordinator office - eight floor

b. corridor near bio-med office - eight floor

c. corridor near eight floor nurse's station

No Description Available

Tag No.: K0047

Based on observation, on April 26, 2011 at approximately 7:30am onward

1. There is no exit sign near cross corridor doors to fourth floor ICU - door 40075C.

No Description Available

Tag No.: K0050

Based on observation, on April 27, 2011 at approximately 5:30am onward:

1. Staff in operating room suite was not familiar with unlabeled air handler shutdown switch - located at abandoned room in third floor north tower.

No Description Available

Tag No.: K0051

Based on observation, on April 25, 2011 at approximately 1:00pm onward,

1. There is no smoke detector located within eight floor nurse's station area - near door hold-open device located in required smoke barrier.

No Description Available

Tag No.: K0056

Based on observation, on April 27, 2011 at approximately 5:30am onward:

1. There is no sprinklers provided for closets located adjacent to corridors between rooms B-1119 and B-1120 - there are other similar closets on the same floor without sprinklers.


21960


2. Adult ED/ Fast Track - Room across from FT3 - Storage on shelves blocking sprinkler head coverage.

No Description Available

Tag No.: K0061

Based on observation on Monday 4/25/2011 at approx 1:00 PM onward:
1. K61 - potter tamper switches with cords are not approved by NFPA standards for monitoring four sprinkler control valves in main mechanical room.

No Description Available

Tag No.: K0062

Based on observation, on April 26, 2011 at approximately 8:00am onward,

1. Sprinkler system components are incomplete in the following areas:

a. storage room 4B026 - utilizes green bulb sprinklers rated for 90 degrees Celsius.

b. staff lounge hallway sprinkler is cover with lint - near room 4B047.

c. room 4D066 - ceiling furring obstructs pendent sprinkler.

2. Sub-basement pump room - Tamper switch when tested did not send alarm.

No Description Available

Tag No.: K0067

Based on observation, on April 25, 2011 at approximately 1:00pm onward,

1. mechanical systems in the following areas are incomplete:

a. mechanical room PH019 - duct penetrations of vertical chase are not equipped with service access openings and breakaway connections for fire dampers - could not verify installation a time of survey.

b. air handlers #3, and #4 are not equipped with emergency shutdown switch(es) - eight floor.

No Description Available

Tag No.: K0071

Based on observation, on April 27, 2011 at approximately 5:30am onward:

1. The soiled linen chute door will not self-close and latch - fifth floor soiled utility near A-577.

No Description Available

Tag No.: K0072

A. Based on observation, on April 25, 2011 at approximately 1:00pm onward:

1. There is unattended storage of impediments in the corridor near eight floor elevators - items were not in immediate and continuous use. Note: This condition existed thru-out the entire campus in several areas.

2. Flat screen monitors, mounted on corridor walls, extend greater than three and one half inches into required corridor headroom clearance - located in area containing room R-408.


3. 7th Floor - Wall mounted charting tables in the corridor that were not self retracting/closing

4. Linen Closets at room R709 - with Corridor doors not self closing or open 180 degrees.

No Description Available

Tag No.: K0076

Based on observation, on April 27, 2011 at approximately 8:00am onward,

1.There are full and empty oxygen cylinders are intermingled in the same storage racks - north tower, third floor operating room suite, 5th Floor Respitory Therapy.

No Description Available

Tag No.: K0077

Based on observation on Monday 4/25/2011 at approximately 1:00 PM onward:

1. Oxygen/ Med Gas gauges not registering correctly - could not test alarms.

No Description Available

Tag No.: K0145

Based on observation, on April 26, 2011 at approximately 8:00am onward,

1. There is no lighting identified on the Critical Branch of the essential electrical system in the following area:

a. eight floor nurse's station

2. Fire alarm power supply, circuit #27, is wired to critical branch panelboard CL-4-C - panelboard is located in room 4D068.

No Description Available

Tag No.: K0147

Based on observation, on April 25, 2011 at approximately 1:00pm onward,

1. electrical systems are incomplete in the following areas:

a. exposed bulb fluorescent light fixture is used above storage shelf - penthouse floor storage room near cafeteria.

b. medication refrigerator in medication preparation room is connected to normal power receptacle - eight floor.

c. light in medication preparation room is not connected to the critical branch of the essential electrical system - eight floor.