Tag No.: K0012
Based on observation, on April 25, 2011 at approximately 1:00pm onward:
1. Room # A468, there were penetrations in rated walls that were not properly sealed to maintain the required fire rating of the walls.
Tag No.: K0018
Based on observation, on April 25, 2011 at approximately 1:00pm onward:
1. 8th Floor, North Tower,- Hemo, Corridor door with self closing device held open with Electro-Magnetic device , did not close upon activation of Fire Alarm as required.
Tag No.: K0020
Based on observation, on April 25, 2011 at approximately 1:00pm onward:
1. The fire door to the eight floor diverter shaft 125 is not self-closing and latching.
Tag No.: K0025
Based on observation, on April 27, 2011 at approximately 5:30am onward:
1. There is a hole in the smoke barrier wall above doors 904A.
Tag No.: K0027
Based on observation, on April 25, 2011 at approximately 1:00pm onward:
1. 4 th Floor - Cross Corridor smoke doors ( # 077B) and (# A457) did not close for smoke tight seal when tested.
Tag No.: K0029
Based on observation, on April 26, 2011 at approximately 7:30 am onward,
1. There are holes in the door to housekeeping room M055 - the door equipped with a hasp that prevents exiting from inside the room.
2. Electrical rooms R-701 & 702 - 2-hr rated walls - There was no fire damper in Exhaust duct thru walls.
Tag No.: K0032
Based on observation, on April 26, 2011 at approximately 7:30am onward,
1. The special locking arrangements for selected doors are noncompliant based upon the following:
a. lack of complete installation in accordance with required building codes - locks at doors 40075C and CCU (7th floor) are not provided with a master release on/off switch at a supervised nurse's station.
2. 6th Floor , Stairwell #61, Exit door equipped with Mag- locks did not release with activation of Fire Alarm, the door did release with over ride switch at door. This must be corrected immediately.
Tag No.: K0033
Based on observation, on April 26, 2011 at approximately 7:30am onward,
1. There is approximately a half inch gap between the meeting edge of fire doors RT01 - the astragal provided is not sufficient to maintain required fire rating.
Tag No.: K0038
Based on observation, on April 26, 2011 at approximately 7:30am onward,
1. The exit access doors require greater than a thirty pound force to set the doors in motion - doors from Chinese garden.
Tag No.: K0040
Based on observation, on April 26, 2011 at approximately 7:30am onward,
1. The horizontal sliding door to room R419 is used as an exit access door - the doors to similar rooms are not located within a suite of rooms.
Tag No.: K0045
Based on observation Monday , 4/25/2011 at approximately 1:00 PM onward :
1. 9th Floor : There was no lighting on Emergency Circuit ( LS Branch) for family waiting room # 90064
2. There was not exit discharge lighting in the exit discharge path from the first floor Reynolds to West & Watlington. (1st floor Reynolds)
Tag No.: K0046
Based on observation, on April 25, 2011 at approximately 1:00pm onward,
1. There is no lighting identified on the Life Safety Branch of the essential electrical system in the following areas:
a. central corridor near the dialysis coordinator office - eight floor
b. corridor near bio-med office - eight floor
c. corridor near eight floor nurse's station
Tag No.: K0047
Based on observation, on April 26, 2011 at approximately 7:30am onward
1. There is no exit sign near cross corridor doors to fourth floor ICU - door 40075C.
Tag No.: K0050
Based on observation, on April 27, 2011 at approximately 5:30am onward:
1. Staff in operating room suite was not familiar with unlabeled air handler shutdown switch - located at abandoned room in third floor north tower.
Tag No.: K0051
Based on observation, on April 25, 2011 at approximately 1:00pm onward,
1. There is no smoke detector located within eight floor nurse's station area - near door hold-open device located in required smoke barrier.
Tag No.: K0056
Based on observation, on April 27, 2011 at approximately 5:30am onward:
1. There is no sprinklers provided for closets located adjacent to corridors between rooms B-1119 and B-1120 - there are other similar closets on the same floor without sprinklers.
21960
2. Adult ED/ Fast Track - Room across from FT3 - Storage on shelves blocking sprinkler head coverage.
Tag No.: K0061
Based on observation on Monday 4/25/2011 at approx 1:00 PM onward:
1. K61 - potter tamper switches with cords are not approved by NFPA standards for monitoring four sprinkler control valves in main mechanical room.
Tag No.: K0062
Based on observation, on April 26, 2011 at approximately 8:00am onward,
1. Sprinkler system components are incomplete in the following areas:
a. storage room 4B026 - utilizes green bulb sprinklers rated for 90 degrees Celsius.
b. staff lounge hallway sprinkler is cover with lint - near room 4B047.
c. room 4D066 - ceiling furring obstructs pendent sprinkler.
2. Sub-basement pump room - Tamper switch when tested did not send alarm.
Tag No.: K0067
Based on observation, on April 25, 2011 at approximately 1:00pm onward,
1. mechanical systems in the following areas are incomplete:
a. mechanical room PH019 - duct penetrations of vertical chase are not equipped with service access openings and breakaway connections for fire dampers - could not verify installation a time of survey.
b. air handlers #3, and #4 are not equipped with emergency shutdown switch(es) - eight floor.
Tag No.: K0071
Based on observation, on April 27, 2011 at approximately 5:30am onward:
1. The soiled linen chute door will not self-close and latch - fifth floor soiled utility near A-577.
Tag No.: K0072
A. Based on observation, on April 25, 2011 at approximately 1:00pm onward:
1. There is unattended storage of impediments in the corridor near eight floor elevators - items were not in immediate and continuous use. Note: This condition existed thru-out the entire campus in several areas.
2. Flat screen monitors, mounted on corridor walls, extend greater than three and one half inches into required corridor headroom clearance - located in area containing room R-408.
3. 7th Floor - Wall mounted charting tables in the corridor that were not self retracting/closing
4. Linen Closets at room R709 - with Corridor doors not self closing or open 180 degrees.
Tag No.: K0076
Based on observation, on April 27, 2011 at approximately 8:00am onward,
1.There are full and empty oxygen cylinders are intermingled in the same storage racks - north tower, third floor operating room suite, 5th Floor Respitory Therapy.
Tag No.: K0077
Based on observation on Monday 4/25/2011 at approximately 1:00 PM onward:
1. Oxygen/ Med Gas gauges not registering correctly - could not test alarms.
Tag No.: K0145
Based on observation, on April 26, 2011 at approximately 8:00am onward,
1. There is no lighting identified on the Critical Branch of the essential electrical system in the following area:
a. eight floor nurse's station
2. Fire alarm power supply, circuit #27, is wired to critical branch panelboard CL-4-C - panelboard is located in room 4D068.
Tag No.: K0147
Based on observation, on April 25, 2011 at approximately 1:00pm onward,
1. electrical systems are incomplete in the following areas:
a. exposed bulb fluorescent light fixture is used above storage shelf - penthouse floor storage room near cafeteria.
b. medication refrigerator in medication preparation room is connected to normal power receptacle - eight floor.
c. light in medication preparation room is not connected to the critical branch of the essential electrical system - eight floor.