Tag No.: K0032
Based on observation, on April 26, 2011 at approximately 7:30am onward,
1. The special locking arrangements for selected doors are noncompliant based upon the following:
a. lack of complete installation in accordance with required building codes - locks at doors 40075C and CCU (7th floor) are not provided with a master release on/off switch at a supervised nurse's station.
2. 6th Floor , Stairwell #61, Exit door equipped with Mag- locks did not release with activation of Fire Alarm, the door did release with over ride switch at door. This must be corrected immediately.
Tag No.: K0040
Based on observation, on April 26, 2011 at approximately 7:30am onward,
1. The horizontal sliding door to room R419 is used as an exit access door - the doors to similar rooms are not located within a suite of rooms.
Tag No.: K0056
Based on observation on Monday 4/25/2011 at approximately 1:00 PM onward:
1. AHU #18 mechanical room has sprinkler head that is blocked partially by a duct. (9 North)
2. Electrical room next to pharmacy did not have a sprinkler head (3rd floor North room # 3B0006)
3. Telecommunication room, next to equipment room, did not have a sprinkler head (3rd floor North, room # 3B005)