HospitalInspections.org

Bringing transparency to federal inspections

1000 SOUTH BECKHAM AVE

TYLER, TX 75701

General Requirements - Other

Tag No.: K0100

Based on observation the facility failed to provide proper labeling for rated walls.
All fire walls, fire barriers, fire partitions, smoke barriers, and smoke partitions shall be effectively and permanently identified with signs or stenciling per IBC 2012 section 703.7.

Means of Egress Requirements - Other

Tag No.: K0200

Based on observation the facility failed to provide clear EXIT SIGN location. Relocate exit sign in front of clean room as to not confuse existing door to room as an exit sign.

Directional Exit Signs, A sign complying with 7.10.3 with a directional indicator showing the direction of travel shall be placed in every location where the direction of travel to reach the nearest exit is not apparent. - NFPA 101, 2003 7.10.2.

Protection - Other

Tag No.: K0300

Based on observation the facility failed to provide a complete protected fire assembly on 4th floor W smoke compartment wall .

"Penetrations for cables, cable trays, conduits, pipes, tubes, combustion vents and exhaust vents, wires, and similar items to accommodate electrical, mechanical, plumbing, and communications systems that pass through a wall, floor, or floor/ceiling assembly constructed as a fire barrier shall be protected by a firestop system or device." - NFPA 101, 2012, 8.3.5.1.

Electrical Systems - Other

Tag No.: K0911

Based on observation the facility failed to provide proper securement for wires on 6th floor south, 4th floor west. This is a general comment, for all floors.
Where independent support wires are used, they shall be secured at both ends. Cables and raceways shall not be supported by ceiling grids." - NFPA 70, 2002, 300.11



Based on observation the facility failed to provide cover for a j-box on second floor room 1S82N.
"Covers. All pull boxes, junction boxes, and conduit bodies shall be provided with covers compatible with the box or conduit body construction and suitable for the conditions of use. Where used, metal covers shall comply with the grounding requirements of 250.110." NFPA 70, 2011, 314.28 (C)



Based on observation the facility failed to provide proper label for FACP circuit on LS panel.
"The circuit breaker at the electrical panel board for the fire alarm shall have a red marking, shall be accessible only to authorized personnel, and shall be identified as "FIRE ALARM CIRCUIT CONTROL"" - NFPA 72, 2010: 10.5.5.2.2

Electrical Systems - Essential Electric Syste

Tag No.: K0917

Based on observation the facility failed to provide proper markings for critical plugs within facility.
"The electrical receptacles or the cover plates for the electrical receptacles supplied from the emergency system shall have a distinctive color or marking so as to readily identifiable." - NFPA 99, 2012, 4.4.2.2.4.2(B).

Features of Fire Protection - Other

Tag No.: K0932

Based on observation the facility failed to provide proper protections for sprinkler heads located inside freezer /coolers.
6.2.8? Guards. Sprinklers subject to mechanical injury shall be protected with listed guards.