Tag No.: K0025
Based on observation the facility failed to provide smoke barriers that would provide at least a one half hour fire resistance rating in accordance with the LSC sections 19.3.7.3, 19.3.7.5, 19.1.6.3, 19.1.6.4.
Findings include:
On 7/15/10, at approximately 1:00 p.m., during inspections of smoke barrier walls with the Facility Director, the following observations were made.
1. Corrected 9/15/10
2. Corrected 9/15/10
3. Corrected 9/15/10
4. Corrected 9/15/10
5. Corrected 9/15/10
6. Corrected 9/15/10
7. Corrected 9/15/10
8. Corrected 9/15/10
9. Corrected 9/15/10
On 7/19/10, at approximately 10:00 a.m., during inspections of smoke barrier walls with the Facility Director, the following observations were made.
1. Corrected 9/15/10
2. Observed the east smoke barrier wall of the joint camp room to have several penetrations through the wall, and the smoke barrier wall not finished to the deck. Observation with the Facility Director during the 9/22/10 survey confirms that this remains uncorrected. Observation with the Facility Director during the 12/22/10 survey confirms that this remains uncorrected.
3. Corrected 12/22/10
4. Corrected 12/22/10
5. Corrected 12/22/10
6. Corrected 12/22/10
7. Corrected 9/15/10
8. Corrected 9/15/10
9. Corrected 9/15/10
10. Observed the smoke barrier wall next to room # 3379 not finished to the deck as required. Observation with the Facility Director during the 9/22/10 survey confirms that this remains uncorrected. Observation with the Facility Director during the 12/22/10 survey confirms that this remains uncorrected.
11. Corrected 9/15/10
12. Corrected 9/15/10
13. Corrected 9/15/10
14. Corrected 9/15/10
15. Corrected 9/15/10
16. Corrected 9/15/10
17. Corrected 9/15/10
18. Corrected 9/15/10
19. Corrected 9/15/10
On 7/27/10, at approximately 2:00 p.m., during inspections of smoke barrier walls with the Facility Director, the following observations were made.
1. Corrected 9/15/10
2. Corrected 9/15/10
3. Corrected 9/15/10