HospitalInspections.org

Bringing transparency to federal inspections

702 N MAIN ST

OPP, AL 36467

No Description Available

Tag No.: K0051

27382


The facility failed to provide a fire alarm system per code. Findings include:

During the revisit, based on interview with the Maintenance Director plans should be sent in to plan review soon. The facility had requested an revised waiver request on the last revisit of 07/31/2013.

During the revisit, based on interview with the Maintnance Director bids are being attain by the facility for cost of correction, facility has a waiver approved until 10/31/2012.

1. The surveyor could not verify that the fire alarm system was on a dedicated circuit

2. While testing the fire alarm system phone lines (DACT):

a. The facility did not get a trouble for line two
b. The facility did not get a trouble for both phone lines (communication)

1999 NFPA 72, Table 7-2.2
b. Digital Alarm Communicator Transmitter (DACT)
The primary line from the DACT shall be disconnected. Indication of the DACT trouble signal at the premises shall be verified as well as transmission to the supervising station within 4 minutes of detection of the fault.
The secondary means of transmission from the DACT shall be disconnected. Indication of the DACT trouble signal at the premises shall be verified as well as transmission to the supervising station within 4 minutes of detection of the fault.
.
Second Floor
3. The surveyor could verify that the Geri-Psych doors released under loss of primary power to the fire alarm system

________________________
NFPA 101 Sections 19.3.4.1 and 9.6. The indication shall be an audible and visual notification at location where it is likely to be heard in the facility.

1999 NFPA 72, 1-5.2.5.2 Connections to the light and power service shall be on a dedicated branch circuit(s). The circuit(s) and connections shall be mechanically protected. Circuit disconnecting means shall have a red marking, shall be accessible only to authorized personnel, and shall be identified as FIRE ALARM CIRCUIT CONTROL. The location of the circuit disconnecting means shall be permanently identified at the fire alarm control unit.

1999 NFPA 72, Table 7-2.2 b. Digital Alarm Communicator
Transmitter (DACT)
The primary line from the DACT shall be disconnected. Indication of the DACT trouble signal at the premises shall be verified as well as transmission to the supervising station within 4 minutes of detection of the fault.

The secondary means of transmission from the DACT shall be disconnected. Indication of the DACT trouble signal at the premises shall be verified as well as transmission to the supervising station within 4 minutes of detection of the fault.

1999 NFPA 72, 3-9.7.3 All exits connected in accordance with 3-9.7.1 shall unlock upon loss of the primary power to the fire alarm system serving the protected premises. The secondary power supply shall not be utilized to maintain these doors in the locked condition.

No Description Available

Tag No.: K0051

The facility failed to provide a fire alarm system per code. Findings include:

During the revisit, based on interview with the Maintenance Director plans should be sent in to plan review soon. The facility had requested an revised waiver request on the last revisit of 07/31/2013.

During the revisit, based on interview with the Maintnance Director bids are being attain by the facility for cost of correction, facility has a waiver approved until 10/31/2012.

1. The surveyor could not verify that the fire alarm system was on a dedicated circuit

2. While testing the fire alarm system phone lines (DACT):

a. The facility did not get a trouble for line two
b. The facility did not get a trouble for both phone lines (communication)

1999 NFPA 72, Table 7-2.2
b. Digital Alarm Communicator Transmitter (DACT)
The primary line from the DACT shall be disconnected. Indication of the DACT trouble signal at the premises shall be verified as well as transmission to the supervising station within 4 minutes of detection of the fault.
The secondary means of transmission from the DACT shall be disconnected. Indication of the DACT trouble signal at the premises shall be verified as well as transmission to the supervising station within 4 minutes of detection of the fault.
.
Second Floor
3. The surveyor could verify that the Geri-Psych doors released under loss of primary power to the fire alarm system

________________________
NFPA 101 Sections 19.3.4.1 and 9.6. The indication shall be an audible and visual notification at location where it is likely to be heard in the facility.

1999 NFPA 72, 1-5.2.5.2 Connections to the light and power service shall be on a dedicated branch circuit(s). The circuit(s) and connections shall be mechanically protected. Circuit disconnecting means shall have a red marking, shall be accessible only to authorized personnel, and shall be identified as FIRE ALARM CIRCUIT CONTROL. The location of the circuit disconnecting means shall be permanently identified at the fire alarm control unit.