Tag No.: K0047

Based on observations made during the survey of the facility (PANHANDLE) while accompanied by the Acting Administrator, and Facility Services Manager it was observed that the facility failed to provide the required Exit Signage for the locations in the facility:
1. PSU CORRIDOR intersection (1 sign to be added).
2. PSU CORRIDOR near PRE-ADMIT (1 sign to be added).

No Description Available

Tag No.: K0050

Based on observations made during the survey of the facility (PANHANDLE) while accompanied by the Acting Administrator, and Facility Services Manager it was observed that although the facility was able to provide a log indicating consistent, systematic compliance with time requirements for performing quarterly fire drills on each shift, the names/signatures of the individual staff memebers who participated were not recorded. The documentation process was incomplete.

No Description Available

Tag No.: K0052

Based on observations made during the survey of the facility (PANHANDLE) while accompanied by the Acting Administrator, and Facility Services Manager it was observed that the facility failed to provide a log indicating compliance with requirement for monthly testing by staff of the fire alarm system and its automatic signal response.

No Description Available

Tag No.: K0130

Based on observations made during the survey of the facility (PANHANDLE) while accompanied by the Acting Administrator, and Facility Services Manager it was observed that while it appears the facility had accomplished some of the requirements, the facility failed to provide logs indicating consistent, systematic compliance on the following issues and items:

1. Electrical equipment inspections - Biomedical.
Critical Areas: Semi-annually.
General Areas: Annually
2. Electrical power and distribution and grounding systems - Effectiveness.
Critical Areas: Semi-annually.
General Areas: Annually

No Description Available

Tag No.: K0144

Based on observations made during the survey of the facility (PANHANDLE) while accompanied by the Acting Administrator, and Facility Services Manager it was observed that the facility failed to provide an Emergency Generator log indicating consistent, systematic compliance on the following issues and items:

1. Weekly inspections.