Tag No.: K0200
Based on observation the facility failed to provide adequate positive latching for exit door adjacent to hospital room 23.
"Doors shall be self-latching and provided with positive latching hardware." - NFPA 101: 2012: 18.3.6.3.5
Based on observation the facility failed to provide adequate latching requirements for corridor doors. Facility to verify that all patient room doors are provided with a closer.
"Doors (Corridor Doors) shall be self-latching and provided with positive latching hardware." - NFPA 101, 2012: 18-3.6.3.5
Based on observation the facility failed to provide documents for required testing of doors in the means of egress.
Tag No.: K0500
Based on observation the facility failed to provide updated documents for monthly maintanace service for HVAC units filters.
Tag No.: K0911
Based on observation the facility failed to provide low voltage wires from resting on ceiling grid and tiles.
Raceways, cable assemblies, boxes, cabinets, and fittings shall be securely fastened in place. Support wires that do not provide secure support shall not be permitted as the sole support.