Bringing transparency to federal inspections
Tag No.: K0046
Based on observation, the facility failed to install battery powered emergency lighting in the operating room.
Findings include :
While on tour April 24, 2013, at 12:35 PM, with the facility Maintenance Director, in the operating room, there were no battery powered lights observed. NFPA 70 (1999 edition) article 517-63 (a) requires battery-powered lights in anesthetizing locations. The facility conducts invasive procedures for which lighting is required for the ten seconds allowed until the emergency generator provides power during a power outage.
Tag No.: K0061
Based on observation, the facility failed to supervise fire sprinkler control valves.
Findings include :
While on tour April 24, 2013, at 11:54 AM, with the facility Maintenance Director, at the facility West property line, adjacent to the street, the back-flow prevention assembly , serving potable and fire sprinkler water to the facility was observed with no electrical supervision on two control valves. NFPA 101 (2000 edition) ' chapter 9.7.1.1 requires at least a local alarm sound when the valves are closed two turns or more.
Tag No.: K0070
Based on observation, the facility failed to prevent the use of prohibited space heaters in the facility.
Findings include :
While on tour on April 24, 2013, at 12:19 PM, with the facility Maintenance Director, in the pharmacy office, a space heater not listed for use by a health care facility was observed under a desk. The space heater required a three foot separation from combustibles. NFPA 101(2000 edition) chapter 19.7.8 prohibits space heaters in a health care facility. Non sleeping employee areas may have space heaters if the element does not exceed 212 degrees Fahrenheit.
Tag No.: K0211
Based on observation, the facility failed to maintain a safe separation between alcohol based hand rub (abhr) and a source of ignition (light switch)
Findings include :
While on tour April 24, 2013, from 11:54 AM to 1:15 PM with the facility Maintenance Director, abhr dispensers were observed less than one inch to the side of a source of ignition (light switch) in the following locations :
1. In the emergency room
2. In room 129
If ignited, abhr can injure patients, visitors and staff.