Tag No.: K0050
Facility failed to maintain complete records of fire drills for 2013 in accordance with the 2000 edition of the Life Safety Code NFPA (National Fire Protection Association) 101. Findings included the following:
Surveyor observed between 9:00 and 9:30 am on 12/12/13 that 3rd quarter 2013 fire drill was missing from records.
Tag No.: K0145
Facility failed to maintain Type I EES in accordance with the 1999 edition of NFPA 99, Health Care Facilities. Findings included the following:
Surveyor observed between 9:00 and 9:30 am on 12/12/13 that electrical system upgrades from previous survey were not completed including electrical panels B1, B2, and B3 and associated transfer gear to be labeled appropriately. On going design efforts were identified by plant engineer and shall be continued to bring Type I EES into compliance.