840 NORTH OAK AVENUE

RULEVILLE, MS 38771

No Description Available

Tag No.: K0012

Based on observation the facility failed to provide the correct building construction type in accordance with 19.1.6.2,19.1.6.3, 19.1.6.4, 19.3.5.1. This deficient practices have the potential of effecting the entire facility.

The maintenance supervisor and the administrator were notified during an exit conference.

Findings include:

While inspecting the building construction type on August 7,2012 at 11:00 a.m., the surveyor and maintenance director observed a mechanical closet built inside the pharmacy was constructed of noncomforming combustible material.

The maintenance supervisor and the administrator were notified during an exit conference.

No Description Available

Tag No.: K0025

Based on observations the facility failed to provide the required 30 minute fire resistance rating for smoke barrier walls in accordance with 19.3.7.3, 19.1.6.3, 19.1.6.4. This condition has the potential to affect about 50% of the residents and staff.

Finding include:

While inspecting smoke barrier walls on August 7, 2012 at 10:30 a.m., the maintenance supervisor and the surveyor observed the smoke barrier walls had the following unsealed penetrations:
1. Smoke barrier wall near the kitchen was sealed with material having no fire resistive characteristics.
2. Smoke barrier wall near main entrance was sealed with material having no fire resistive characteristics.

The administrator and maintenance director were notified during the survey and in the exit conference.

No Description Available

Tag No.: K0029

Based on observation and testing, the facility failed to provide the one hour fire rated construction (with 45 minute fire-rated doors) or an approved automatic fire extinguishing system in accordance with 8.4.1 and/or 19.3.5.4. This condition affected 25% of the residents and staff or 1 of 4 smoke compartments.

Findings include:

While inspecting hazardous areas on August 7, 2012 at 11:15 a.m., the maintenance supervisor and the surveyor observed the storage room in the kitchen had unsealed penetrations.

The administrator and maintenance director were notified during the survey and in the exit conference.

No Description Available

Tag No.: K0056

Based on observations, the facility failed to provide a supervised automatic sprinkler system with complete coverage for all portions of the building. This condition affected 50% of the residents and staff of the building.

Findings include:

While inspecting the sprinkler system on August 7, 2012 at 11:30 a.m., the maintenance supervisor and the surveyor found that the mechanical closet located inside the pharmacy did not have a sprinkler head installed.

The administrator and maintenance director were notified during the survey and in the exit conference.