Bringing transparency to federal inspections
Tag No.: K0018
Based on observations during the site inspection and discusion with the maintenance supervisor on 02/25/2010, two sets of corridor doors at the dietary department (one providing access to the dining area, and one providing access to the kitchen) were being held in the open position. They lacked self-closing devices. Magnetci hold-open devices were being installed, but not yet activated.
Tag No.: K0051
Based on observations during the site inspection with the maintenance supervisor on the morning of 02/25/2010, the main fire alarm control panel was located in a small closet within the administration area. This closet is a normally unoccupied room and lacked coverage by a smoke detector, as required by NFPA 72 (1999)1-5.6.