774 STATE HIGHWAY 70 N

ROTAN, TX 79546

No Description Available

Tag No.: K0018

Based on observations during the site inspection and discusion with the maintenance supervisor on 02/25/2010, two sets of corridor doors at the dietary department (one providing access to the dining area, and one providing access to the kitchen) were being held in the open position. They lacked self-closing devices. Magnetci hold-open devices were being installed, but not yet activated.

No Description Available

Tag No.: K0051

Based on observations during the site inspection with the maintenance supervisor on the morning of 02/25/2010, the main fire alarm control panel was located in a small closet within the administration area. This closet is a normally unoccupied room and lacked coverage by a smoke detector, as required by NFPA 72 (1999)1-5.6.

LIFE SAFETY CODE STANDARD

Tag No.: K0018

Based on observations during the site inspection and discusion with the maintenance supervisor on 02/25/2010, two sets of corridor doors at the dietary department (one providing access to the dining area, and one providing access to the kitchen) were being held in the open position. They lacked self-closing devices. Magnetci hold-open devices were being installed, but not yet activated.

LIFE SAFETY CODE STANDARD

Tag No.: K0051

Based on observations during the site inspection with the maintenance supervisor on the morning of 02/25/2010, the main fire alarm control panel was located in a small closet within the administration area. This closet is a normally unoccupied room and lacked coverage by a smoke detector, as required by NFPA 72 (1999)1-5.6.