Tag No.: K0351
Based on observation the facility failed to provide adequate protection over an existing supply duct that is over 4' wide in the mechanical penthouse.
Sprinklers shall be installed under fixed obstructions over 4 ft. wide such as ducts, decks, open grate flooring, cutting tables, and overhead doors - NFPA 13, 2002: 8.5.5.3.1.
Tag No.: K0700
Based on observation the facility failed to provide adequate letters indicating preferred customers status in case of emergency situation for water and fuel source.
Tag No.: K0900
Based on observation the facility failed to provide adequate signage for an existing low headroom location at mechanical penthouse.
HLR 133.132 (d)(2)(A)(xii)(III) Overhead clearance. Suspended tracks, rails, pipes, signs, lights, door closers, exit signs, and other fixtures that protrude into the path of normal traffic shall not be less than six feet eight inches above the finished floor.
Tag No.: K0917
Based on observation the facility failed to provide adequate identification to critical care outlets with non-removable labels-circuit and panel.