Tag No.: K0076

Based on observation, it was determined that the facility failed to protect gas in storage in accordance with NFPA 99 4-3.1.1.1.

Findings include:

1. On 6/14/12 at 9:40 AM, in the presence of Staff #6, one (1) tank of gas located in the tank farm was not secured. NFPA 99 4-3.1.1.1 states cylinders in service and in storage shall be secured and located to prevent falling or being knocked over.

2. On 6/14/12 at 9:40 AM, in the presence of Staff #6, four (4) tanks of gas located in the Observation Unit were not secured. NFPA 99 4-3.1.1.1 states cylinders in service and in storage shall be secured and located to prevent falling or being knocked over.