500 NORTH CLARENCE NASH BOULEVARD

WATONGA, OK 73772

Subdivision of Building Spaces - Smoke Barrie

Tag No.: K0372

Based on observation and interview, the facility failed to maintain 2 of 4 smoke barrier walls to resist the passage of smoke. Findings:

1. A tour of the facility was conducted on 10/15/24 and the following observations were made.

a) One unsealed penetration, associated with a computer wires was observed above the smoke doors next to the conference room.

b) One unsealed penetration, associated with a computer wires was observed above the smoke doors at the beginning of the Therapy hall.

2. The Plant manager was present when the smoke walls were observed on 10/15/24, and he acknowledged the unsealed penetrations to the smoke walls.

Fire Drills

Tag No.: K0712

Based on record review and staff interview, the facility failed to assure the minimum required number of fire drills were conducted within the past year. Findings:

1. Review of the facility fire drill reports was conducted on 10/15/2024. There was no documentation the facility had conducted a fire drill for the following shift:

a. the second shift for the second quarter of 2024.

b. the first shift for the third quarter of 2024.

2. The Plant manager was interviewed on 10/15/2024 and stated the facility missed the fire drills for those two shifts.