HospitalInspections.org

Bringing transparency to federal inspections

3080 COLLEGE STREET

BEAUMONT, TX 77701

No Description Available

Tag No.: K0022

Facility failed to maintain access to exits in accordance with the 2000 edition of the Life Safety Code, NFPA 101. Findings included the following:

Surveyor observed between 10:00 and 11:00 on 2/06/13:
1. exit signage at Sabine building, 2nd floor ICU led to mag locked doorway connection to Trinity Tower which did not release upon initiation of fire alarm in accordance with NFPA 101, 2000: 7.10.1.4.

No Description Available

Tag No.: K0038

Facility failed to maintain exit access in accordance with the 2000 edition of the Life Safety Code, NFPA 101. Findings included the following:

Surveyor observed between 10 and 11 am on 02/06/13 that corridor walking surface outside the MRI in the first floor of the Sabine Building was not in accordance with NFPA 101, 200: 7.1.6.

No Description Available

Tag No.: K0067

Facility failed to maintain building systems in accordance with NFPA 90A, standard for Heating, ventilating and Air Conditioning. Findings include:

Surveyor observed between 10 and 11am on 02/06/13 that ceiling tiles were stained in teh central supply room in the first floor of the Necheds buiding.

No Description Available

Tag No.: K0069

Facility failed to maintain cooking equipment protection in accordance with the Standard for fire Extinguishers, NFPA 10. Findings included the following:

Surveyor observed between 11 and 11:30 am on 02/06/13 that one of two "K" type extinguishers were not properly placarded to read "fire protection system shall be activated prior to using fire extinguisher" in accordance with NFPA 10:4.3.2.2.

No Description Available

Tag No.: K0145

Facility failed to perform electrical receptacle testing in accordance with the Standard for Health Care, NFPA 99. Findings included the following:

Surveyor observed between 2:00 and 2:30 pm on 2/06/13 that facility records do not include receptacle testing in patient care areas in accordance with NFPA 99:3-3.3.3 and 7-6.2.1.2. Receptacles shall be tested in Patient Care areas as follows:

Phyisical integrity of each receptacle (visual)
Continuity of the grounding of each receptacle (test)
Correct polarity of hot and neutral connections in each receptacle (test)
The retention force of the grounding blade shal be not less than 4 oz. (test)

Testing intervals:
General care areas tested annually
Critical care areas tested semi-annually
wet location tested annually.

No Description Available

Tag No.: K0147

Facility failed to maintain electrical systems in accordance with the National electrical code, NFPA 70. Findings include:

Surveyor observed between 11 and 11:30 am on 2/06/13 that in the dietary department, two of four electrical panels, labeled "KA" and "KD" were not properly secured in locked position in accordance with NFPA 70:110-17.