Tag No.: K0012

Based on observation during the life safety survey completed on 09/09/14, the facility did not maintain construction elements to be in reliable condition as required.

Findings:

Two 2" holes were observed in the ceiling and wall of the x-ray room.

This observation was made in the presence of the Director of Plant Operations.

No Description Available

Tag No.: K0017

Based on observation during the life safety survey completed on 09/09/14, the facility did not maintain corridor walls to resist the passage of smoke and toxic fumes as required.

Findings:

Two 1' holes were observed in the corridor wall above the lay-in ceiling in the area across from the Radiology Manager's Office.

This observation was made in the presence of the Director of Plant Operations.

No Description Available

Tag No.: K0018

Based on observation during the life safety survey completed on 09/09/14, the facility did not maintain corridor doors to be positive latching as required.

Findings:

The following corridor doors did not close to positive latch when tested: Rooms 23, 28, 30 and 34.

These observations were made in the presence of the Director of Plant Operations.

No Description Available

Tag No.: K0029

Based on observation during the life safety survey completed on 09/09/14, the facility did not maintain hazardous area doors to be self closing and positive latching as required.

Findings:

1. The water heater room door was observed to be lacking a self-closing device.

2. The boiler room door was observed to be lacking a self-closing device.

These observations were made in the presence of the Director of Plant Operations.

No Description Available

Tag No.: K0054

Based on a review of smoke detector testing documentation during the life safety survey completed on 09/09/14, the facility did not maintain required testing intervals of smoke detector testing as required per NFPA 72.

Findings:

The facility could not provide documentation that smoke detectors are being sensitivity tested at least every two years as required.

No Description Available

Tag No.: K0147

Based on observation during the life safety survey completed on 09/09/14, the facility did not maintain electrical equipment and power cords to be in compliance with NFPA 70, The National Electrical Code, as required.

Findings:

1. Two open breaker ports were observed in electrical panel H-2.

2. A microwave oven was observed to be energized via a portable power strip in the break room.

3. An electric fan was observed to be energized via a portable power strip in the Rec Therapy Room.

4. An extension cord was observed in use connected to a steam table in the Dining Room.

These observations were made in the presence of the Director of Plant Operations.