Bringing transparency to federal inspections
Tag No.: K0033
Based on observation and record review, the provider failed to maintain a one hour fire rated protective path of egress from a stair enclosure to the exterior of the building. Findings include:
1. Observation at 2:00 p.m. revealed the west basement stair enclosure discharged into the x-ray department on the first floor.
Observation at 3:00 p.m. revealed the west stair enclosure on the second floor discharged into the corridor of the 2000 addition.
A continuous path of escape was not provided to the exterior of the building. Review of the previous life safety code survey confirmed those conditions had existed since completion of the 2000 addition.
The building meets the FSES. Please mark an "F" in the completion date column to indicate the provider's intent to correct the deficiencies identified at K000.