HospitalInspections.org

Bringing transparency to federal inspections

50 KIRKBRIDE DRIVE

DANVILLE, PA 17821

No Description Available

Tag No.: K0011

Based on observation and interview it was determined the facility failed to properly maintain 2-hour fire rated common walls affecting two of four floors in this component.

Findings include:

A. Observation on July 12, 2012, between 10:31 AM and 1:31 PM, revealed the following deficiencies:

1. 10:31 AM - First floor, common wall above door 1056 is not sealed tight to the deck above, open where corrugated roof meets top of wall.

2. 1:31 PM - Basement level, common wall around door 001 has unprotected penetrations and remaining sheet metal plate does not provide a 2-hour fire resistance rating.

Exit interview with maintenance representative #1, maintenance representative #2, and design professional #1 on July 13, 2012 between 11:00 AM and 11:30 AM, confirmed these 2-hour fire rated common wall deficiencies.

No Description Available

Tag No.: K0012

Based on observation and interview it was determined the facility failed to properly maintain building construction on four of four floors in this component.

Findings include:

A. Observation on July 11, 2012, between 12:40 PM and 1:40 PM, revealed the following deficiencies:

1. 12:40 PM - Fourth floor, typical for all floors below, flooring is comprised of wooden furring strips, wood sub floor and wood finished floor totaling some 2 inches in thickness.

2. 1:00 PM - Fourth floor, typical for all floors below, walls are comprised of individual red bricks and mortar, covered with wooden lath and horse-hair plaster.

3. 1:40 PM - Third floor, typical for all floors below, bathroom has unprotected structural steel within the pipe chase located at door Q314A.

B. Observation on July 12, 2012, at 1:17 PM, revealed unprotected structural steel in the basement level first wet sprinkler riser room.

Exit interview with maintenance representative #1, maintenance representative #2, and design professional #1 on July 13, 2012 between 11:00 AM and 11:30 AM, confirmed these building construction deficiencies.

No Description Available

Tag No.: K0020

Based on observation and interview it was determined the facility failed to properly maintain fire rated vertical enclosures affecting four of four floors in this component.

Findings include:

A. Observation on July 11, 2012, between 12:38 PM and 1:37 PM, revealed the following deficiencies:

1. 12:38 PM - Attic level, numerous vertical air shafts spanning four floors, open directly into the attic space.

2. 12:50 PM - Fourth floor, numerous vertical air shafts, spanning four floors, open directly into horizontal brick air ducts that are partially enclosed.

3. 12:52 PM - Fourth floor, vertical pipe chase, accessed by door 4017, had unprotected penetrations, open to two floors below.

4. 1:30 PM - Third floor, electrical closet 3159 had an unprotected vertical penetration around an electrical conduit at the floor level.

5. 1:37 PM - Third floor, vertical pipe chase, accessed by door Q314A, had unprotected penetrations, open to two floors below.

B. Observation on July 12, 2012, between 8:20 AM and 1:20 PM, revealed the following deficiencies:

1. 8:20 AM - Fourth floor, the second exit stair tower had exposed slate risers and tread when viewed from the 3 ? floor landing. This stair-back was not separated from the stair tower by fire rated construction.

2. 1:12 PM - Basement level, two personal clothes dryer, foil ducts that penetrated the basement ceiling from the first floor lack a required fire rated enclosure.

3. 1:20 PM - Sub-tunnel level, these service tunnels, located below the basement level, are not separated from the basement creating numerous unprotected vertical penetrations in the basement floor.

Exit interview with maintenance representative #1, maintenance representative #2, and design professional #1 on July 13, 2012 between 11:00 AM and 11:30 AM, confirmed these unprotected vertical penetrations.

No Description Available

Tag No.: K0025

Based on observation and interview it was determined the facility failed to properly maintain smoke barrier walls on two of four floors in this component.

Findings include:

A. Observation on July 12, 2012, between 9:01 AM and 10:56 AM, revealed the following unprotected penetrations in the smoke barrier walls:

1. 9:01 AM - Second floor, unprotected penetration around wires above corridor door 2014.

2. 10:56 AM - First floor, unprotected penetration above corridor door 1039.

Exit interview with maintenance representative #1, maintenance representative #2, and design professional #1 on July 13, 2012 between 11:00 AM and 11:30 AM, confirmed these unprotected smoke barrier wall penetrations.`

No Description Available

Tag No.: K0029

Based on observation and interview it was determined the facility failed to properly configure hazardous storage areas on three of four floors in this component.

Findings include:

A. Observation on July 11, 2012, between 12:43 PM and 1:22 PM revealed the following hazardous area deficiencies:

1. 12:43 PM - Fourth floor, combustible storage items stored in the corridor.

2. 1:20 PM - Third floor, Room 3039 used to store combustible materials, had an open transom above the door and lacked a self-closing device.

3. 1:22 PM - Third floor, 3000 corridor, combustible wooden beds stored in the corridor.

B. Observation on July 12, 2012, at 11:11 AM revealed the first floor room 1069, soiled linen storage room, a hazardous area lacked a required self-closing device.

Exit interview with maintenance representative #1, maintenance representative #2, and design professional #1 on July 13, 2012 between 11:00 AM and 11:30 AM, confirmed these hazardous area deficiencies.

No Description Available

Tag No.: K0033

Based upon observation and interview, it was determined the facility failed to maintain five exit stair tower locations within this component.

Findings include:

1. Observation of various exit stair towers within this component between 1:16 p.m. on July 11, 2012, and 1:55 p.m. on July 12, 2012, revealed the below deficiencies:

a. The basement-level portion of the North Bank, third section stair tower enclosure lacks one-hour, fire resistive integrity (less one-hour assembly at ceiling level.) 1:16 p.m.
b. Ceiling height within the fourth floor portion of the North Block, first section stair tower enclosure is less than the required height. 08:22 a.m. on July 12, 2012.
c. The fourth floor ceiling of the 343 stair tower is constructed of horse hair plaster and wooden lathe affixed to combustible roof assembly joists. 09:55 a.m. on July 12, 2012.
d. The basement-level portion of the 302 stair tower enclosure is open to the basement level. 1:55 p.m. on July 12, 2012.
e. An unprotected column was noted within the basement-level North Bank, third section stair tower enclosure wall at 1:17 p.m. on July 11, 2012.

Exit interview with maintenance representative one, maintenance representative two and design professional one during the exit interview process conducted between 11:00 a.m. and 11:30 a.m. on July 13, 2012, confirmed the above stair tower enclosure deficiencies.

No Description Available

Tag No.: K0034

Based on observation and interview it was determined the facility failed to properly configure one of six exit stair towers in this component.

Findings include:

A. Observation on July 11, 2012, at 12:34 PM, revealed the fourth floor exit stair tower landing, located at door 4002, had reduced head room measuring 6 feet 4 inches.

Exit interview with maintenance representative #1, maintenance representative #2, and design professional #1 on July 13, 2012 between 11:00 AM and 11:30 AM, confirmed the reduced head room on the fourth floor exit stair tower landing.

No Description Available

Tag No.: K0038

Based upon observation and interview, it was determined the facility failed to maintain exit access in one location on one of four floors.

Findings include:

Observation of the fourth floor, third section area at 10:44 a.m. on July 12, 2012, revealed the ceiling height in this area to be reduced to six feet, two inches for a distance of twelve feet, three inches.

Exit interview with maintenance representative one, maintenance representative two and design professional one during the exit interview process conducted between 11:00 a.m. and 11:30 a.m. on July 13, 2012, confirmed the exit access deficiency.

No Description Available

Tag No.: K0045

Based on observation and interview it was determined the facility failed to

Findings include:

A. Observation on July 11, 2012, at 1:10 PM, revealed the fourth floor corridor at door 4019 lacked the required continuous lighting.

Exit interview with maintenance representative #1, maintenance representative #2, and design professional #1 on July 13, 2012 between 11:00 AM and 11:30 AM, confirmed the fourth floor corridor lacked continuous lighting.

No Description Available

Tag No.: K0047

Based on observation and interview it was determined the facility failed to properly configure exit signage on one of four floors in this component.

Findings include:

A. Observation on July 11, 2012, at 1:12 PM, revealed corridor 4019 lacked exit signage on both ends.

Exit interview with maintenance representative #1, maintenance representative #2, and design professional #1 on July 13, 2012 between 11:00 AM and 11:30 AM, confirmed the fourth floor corridor lacked visible exit signs.

No Description Available

Tag No.: K0054

Based on documentation review and interview it was determined the facility failed to properly test installed smoke detectors on one of four floors in this component.

Findings include:

A. Review of smoke detector testing documentation on July 11, 2012 at 8:15 AM revealed the facility did not have documentation available to verify the installed, non-addressable smoke detectors had required sensitivity testing during the past two years.

Exit interview with maintenance representative #1, maintenance representative #2, and design professional #1 on July 13, 2012 between 11:00 AM and 11:30 AM, confirmed the facility did not have smoke detector sensitivity testing documentation available.

No Description Available

Tag No.: K0056

Based on observation and interview it was determined the facility failed to provide a complete automatic sprinkler system on two of four floors in this component.

Findings include:

A. Observation on July 12, 2012, between 10:25 AM and 1:23 PM, revealed the following areas lacked required automatic sprinkler coverage:

1. 10:25 AM - First floor vestibule at door 1008A lacked sprinkler coverage.

2. 1:23 PM - Sub-Tunnel system lacks sprinkler coverage.

Exit interview with maintenance representative #1, maintenance representative #2, and design professional #1 on July 13, 2012 between 11:00 AM and 11:30 AM, confirmed these areas lacked sprinkler protection.

No Description Available

Tag No.: K0062

Based on documentation review and interview it was determined the facility failed to properly test the installed automatic sprinkler system affecting five of five floors in this component.

Findings include:

A. Review of sprinkler testing and inspection documentation on July 11, 2012 at 8:25 AM, revealed the facility did not have documentation available to support conducting a required annual inspection and testing of the installed automatic sprinkler system.

Exit interview with maintenance representative #1, maintenance representative #2, and design professional #1 on July 13, 2012 between 11:00 AM and 11:30 AM, confirmed the facility did not have annual sprinkler system inspection and testing documentation available.

No Description Available

Tag No.: K0064

Based upon observation and interview, it was determined the facility failed to maintain fire extinguishers in multiple locations on three of three floors.

Findings include:

Observation of flush-mounted fire extinguisher cabinets between 11:33 a.m. and 11:44 a.m. on July 11, 2012, revealed projecting signage lacking in order to aptly identify the fire extinguisher locations.

Exit interview with maintenance representative one, maintenance representative two and design professional one during the exit interview process conducted between 11:00 a.m. and 11:30 a.m. on July 13, 2012, confirmed the fire extinguisher deficiencies.

No Description Available

Tag No.: K0067

Based on documentation review, observation and interview it was determined the facility failed to properly configure or inspect the installed heating, cooling and ventilation (HVAC) system affecting four of four floors in this component.

Findings include:

A. Review of fire and smoke damper inspection documentation on July 11, 2012, between 8:35 AM and 8:40 AM, revealed the facility had the following heating, cooling and ventilation (HVAC) system deficiencies:

1. 8:35 AM - Required 4-year inspection of all installed heating, cooling and ventilation duct fire dampers.

2. 8:40 AM - Required 4-year inspection of all installed heating, cooling and ventilation duct smoke dampers.

B. Observation on July 11, between 12:55 PM and 1:00 PM , revealed the following deficiencies:

1. 12:55 PM - Fourth floor HVAC duct located in room 4016 lacked required retaining angles at the floor level.

2. 1:00 PM - Fourth floor HVAC duct located in room 4016 lacked a fire damper access door.

C. Observation on July 12, at 9:06 AM , revealed the second floor corridor HVAC return, located adjacent to the smoke barrier in the first living area, was not completely ducted to the suspended ceiling below.

Exit interview with maintenance representative #1, maintenance representative #2, and design professional #1 on July 13, 2012 between 11:00 AM and 11:30 AM, confirmed these heating, cooling and ventilation (HVAC) system deficiencies.

No Description Available

Tag No.: K0072

Based on observation and interview it was determined the facility failed to properly maintain exit corridors on two of four floors in this component.

Findings include:

A. Observation on July 12, 2012, between 8:50 AM and 10:40 AM, revealed the following deficiencies:

1. 8:50 AM - Second floor, exit corridor in living area had numerous pieces of stationary furniture in the exit corridor.

2. 10:40 AM - First floor, exit corridor in living area had numerous pieces of stationary furniture in the exit corridor.

Exit interview with maintenance representative #1, maintenance representative #2, and design professional #1 on July 13, 2012 between 11:00 AM and 11:30 AM, confirmed the stationary furniture in the exit corridors located within the living areas.

No Description Available

Tag No.: K0143

Based on observation and interview it was determined the facility failed to properly configure liquid oxygen storage and transfer locations on one of four floors in this component.

Findings include:

A. Observation on July 12, 2012,, at 10:46 AM, revealed the second floor room 1020, was not properly configured as a liquid oxygen transfer or storage location, had three 40 liter liquid oxygen dewars along with portable refillable liquid oxygen containers.

Exit interview with maintenance representative #1, maintenance representative #2, and design professional #1 on July 13, 2012 between 11:00 AM and 11:30 AM, confirmed that room 1020 was not properly configured as a liquid oxygen transfer and storage location.

No Description Available

Tag No.: K0144

Based on observation and interview it was determined the facility failed to properly configure the emergency power supply system on four of four floors in this component.

Findings include:

A. Observation on July 12, at 1:40 PM, revealed the component did not have a required emergency generator derangement signal located at a 24 hour attended location.

Exit interview with maintenance representative #1, maintenance representative #2, and design professional #1 on July 13, 2012 between 11:00 AM and 11:30 AM, confirmed this component did not have a emergency generator derangement signal located at a 24-hour attended location.

No Description Available

Tag No.: K0147

Based on observation and interview it was determined the facility failed to properly maintain the installed electrical distribution system on one of four floors in this component.

Findings include:

A. Observation on July 12, 2012, between 8:53 AM and 9:00 AM,, revealed the following deficiencies:

1. 8:53 AM - Second floor, sleeping room 2011, bed placed against electrical receptacle.

2. 8:55 AM - Second floor, sleeping room 2145, bed placed against electrical receptacle.

3. 8:57 AM - Second floor, sleeping room 2144, bed placed against electrical receptacle.

4. 9:00 AM - Second floor, sleeping room 2143, bed placed against electrical receptacle.

Exit interview with maintenance representative #1, maintenance representative #2, and design professional #1 on July 13, 2012 between 11:00 AM and 11:30 AM, confirmed these electrical distribution system deficiencies.