Tag No.: K0012
Based on observation, on February 7, 2012 at approximately 3:00pm onward, the following items were non-compliant, specific findings include;
A. Smoke door labeled 20 minutes, not 45 minutes, in a one hour rated wall. Birth Center, door to triage.
Tag No.: K0012
Based on observation, on February 7, 2012 at approximately 3:00pm onward, the following items were non-compliant, specific findings include;
A. There is fire protection material missing from structural steel beams in the ROC mechanical room located on basement level.
B. There are penetrations in the ceiling around conduit and sprinkler heads that were not sealed in order to meet the required rating for the area. Basement Loading Dock Area
C. There are penetrations in the ceiling around conduit that were not sealed in order to meet the required rating for the area. 3rd floor mechanical room across from room 3202.
D. Smoke door labeled 20 minutes, not 90 minutes, in a two hour rated wall. 1st floor going into NICU classroom.
Tag No.: K0018
Based on observation, on February 7, 2012 at approximately 3:00pm onward, the following items were non-compliant, specific findings include;
A. Corridor not smoke tight with louver in door to IT room, Birth Center first floor to the right of the security desk, HUB 62.
Tag No.: K0018
Based on observation, on February 7, 2012 at approximately 3:00pm onward, the following items were non-compliant, specific findings include;
A. There are roller latches on exit access doors to imaging rooms #3, #4, and #6. Imaging rooms are located on the basement level.
B. There is no positive latching hardware on exit access doors to SCIU Suite located on the first floor of main hospital.
C. The inactive leaf of exit access doors to operating rooms require greater than a single hand motion to close and latch. The inactive leafs are equipped with manual flush bolt sets. (Located on first floor level)
Tag No.: K0018
Based on observation, on February 7, 2012 at approximately 3:00pm onward, the following items were non-compliant, specific findings include;
A. There was a gap between the double doors to the small storage room door that was not smoke resistant. Sprinkler coverage could not be obtained due to solid shelves. 4th floor Caremont Surgical Suite
Tag No.: K0020
Based on observation, on February 7, 2012 at approximately 3:00pm onward, the following items were non-compliant, specific findings include;
A. Facility at the time of the survey could not verify that the door to the Vertical Chase was a 2-hour rated door. Basement EP Storage
Tag No.: K0025
Based on observation, on February 7, 2012 at approximately 3:00pm onward, the following items were non-compliant, specific findings include;
A. There are unsealed penetrations in the 1 hour smoke barrier above the cross corridor doors at the family waiting room. Main-4th floor - cross corridor doors at the family waiting room
B. There are unsealed penetrations in the 1 hour smoke barrier above the cross corridor doors at the entrance of the PICU-S area. Main-4th floor- PICU-S
Tag No.: K0027
Based on observation, on February 7, 2012 at approximately 3:00pm onward, the following items were non-compliant, specific findings include;
A. The double doors at the smoke barrier leading into the ICU suite on the visitors entrance has a gap grater than 1/8 of an inch. Main 4th floor- ICU Visitors Entrance
Tag No.: K0029
Based on observation, on February 7, 2012 at approximately 3:00pm onward, the following items were non-compliant, specific findings include;
A. Fire doors to hyperbaric unit utilize inactive door leaf without self-closing device and automatic flush bolt assembly. (Wound Center located on third floor)
B. The roof/ceiling assembly of the hyperbaric unit utilizes a non-rated roof suspended ceiling assembly. There is no one hour fire resistive enclosure at the roof/ceiling assembly.
Tag No.: K0029
Based on observation, on February 7, 2012 at approximately 3:00pm onward, the following items were non-compliant, specific findings include;
A. The supply room, and soiled linen room are not equipped with sprinkler or one hour fire resistive enclosure. The roof ceiling assembly of each room is equipped with non-rated suspended ceiling assembly.
Tag No.: K0029
Based on observation, on February 7, 2012 at approximately 3:00pm onward, the following items were non-compliant, specific findings include;
A. The wall between the bulk storage area and pharmacy area at the double doors was not constructed to meet the one hour fire rated construction requirements for the area. Basement Bulk Storage Area
B. The maintenance closet is constructed as a two hour fire rated enclosure and is equipped with a ¾ hr rated door and is not sprinkler. Basement - Pharmacy Maintenance Closet
C. Could not verify the ¾ hour fire resistance rating of the corridor door to the Pharmacy. Basement - Pharmacy
D. The maintenance closet has two ducts penetrating the rated wall that are not equipped with fire dampers. There are holes in the wall that have not been sealed in order to meet the required fire resistance rating of the wall. Basement - Between Bulk Storage Rooms
Tag No.: K0032
Based on observation, on February 7, 2012 at approximately 3:00pm onward, the following items were non-compliant, specific findings include;
A. There is an active dead bolt installed on the patient room door, when the dead bolt is engaged it results in more than a one motion of the hand for egress from the room.
Main - 6th floor- Patient room 6156.
B. Stairway J exits into unprotected glass and steel passageway without an alternate exit from within glass and frame enclosure. The stair door prevents reentry due to access controlled egress lock assembly. The passageway encloses an interior courtyard on the basement level.
C. Stairway J is equipped with an incomplete access controlled egress lock - the exit door from the stair is not equipped with a release switch. The switch must be not greater than five feet from the door.
D. The delayed egress locks are not equipped with a sign on the door that states " Push, alarm will sound " lock will release in fifteen seconds. The locks are located near the maintenance room and triage area on the basement level.
E. Corridor area of imaging center terminates in a room with less than eight feet clear and obstructed path. The room is a waiting room located off the main corridor on the basement level.
F. There are dead-bolt locks on power operated horizontal exit doors - located on basement level near ROC waiting room.
G. The access controlled egress locks did not release during activation of the fire alarm system - Locks are located on the CT, and Imaging area cross corridor doors.
H. Exit egress door with delayed egress did not release with pull station or smoke detector. Corrected during survey. 3rd floor, peds exit stairwell.
Tag No.: K0033
Based on observation, on February 7, 2012 at approximately 3:00pm onward, the following items were non-compliant, specific findings include;
A. Fire doors to east stairway, adjacent to lobby, would not latch.
Tag No.: K0033
Based on observation, on February 7, 2012 at approximately 3:00pm onward, the following items were non-compliant, specific findings include;
A. Fire door to stair did not self latch - located on ground floor at north corridor of surgery center.
Tag No.: K0038
Based on observation, on February 7, 2012 at approximately 3:00pm onward, the following items were non-compliant, specific findings include;
A. There is a deadbolt lock in addition to other positive latching hardware on doors to CT scan #1, and #2.
Tag No.: K0040
Based on observation, on February 7, 2012 at approximately 3:00pm onward, the following items were non-compliant, specific findings include;
A. Exit access doors from restroom A is twenty-two inches in clear opening. Restroom is located in basement level imaging center.
Tag No.: K0045
Based on observation, on February 7, 2012 at approximately 3:00pm onward, the following items were non-compliant, specific findings include;
A. Exit egress lighting was switched and could leave the area in darkness. 7th floor group activities rooms, both North and South front halls.
B. Exit egress lighting was switched and could leave the area in darkness. 7th floor exam rooms, both North and South front halls.
Tag No.: K0046
Based on observation, on February 7, 2012 at approximately 3:00pm onward, the following items were non-compliant, specific findings include;
A. There is no emergency lighting for ground level exit discharge located on north side of facility.
Tag No.: K0046
Based on observation, on February 7, 2012 at approximately 3:00pm onward, the following items were non-compliant, specific findings include;
A. There is no emergency lighting to the public way for courtyard area serving the Chemo & ROC waiting area - located on basement level.
Tag No.: K0046
Based on observation, on February 7, 2012 at approximately 3:00pm onward, the following items were non-compliant, specific findings include;
A. There is no exit discharge lighting to public way - located in first floor exit passageway for north stairway.
Tag No.: K0047
Based on observation, on February 7, 2012 at approximately 3:00pm onward, the following items were non-compliant, specific findings include;
A. Additional exit and directional signs are needed in the exit corridor from the kitchen that will lead to the second mean of egress back to the stairwell. Basement Kitchen Exit Corridor
B. Additional exit and directional signs are needed in the rear exit corridor from the pharmacy. Second means of egress was not marked in the corridor. Basement - Pharmacy rear exit corridor.
C. Exit signage was not provided at exit door to the corridor. Second Floor Scan Center near Locker
Tag No.: K0047
Based on observation, on February 7, 2012 at approximately 3:00pm onward, the following items were non-compliant, specific findings include;
A. There is no exit directional signage leading from the lobby area to the mammography and MRI corridor exits. CIS- Corridors leading to mammography and MRI
Tag No.: K0056
Based on observation, on February 7, 2012 at approximately 3:00pm onward, the following items were non-compliant, specific findings include;
A. No sprinkler coverage of shower stalls in ambulatory surgery center located on the ground floor - shower stalls are located in patient rooms similar to room #3.
This item is not a deficiency per regional office and hense removed.
B. Upper and lower most portion of the stairwell landing not sprinklered in the north stairwell MOB.
Tag No.: K0056
Based on observation, on February 7, 2012 at approximately 3:00pm onward, the following items were non-compliant, specific findings include;
A. The closet has a sprinkler head that is rated 200 degree F intermediate temperature rating in place of 155 degree F ordinary temperature rating. Second floor data closet near medical records passage way
B. The vertical shaft was not equipped sprinkler protection. A, B, C, D, E, F, G and H Vertical Mechanical Chase
C. The sprinkler system was blocked by a solid shower curtain in rooms 7105 and 7252. 7th floor
Tag No.: K0061
Based on observation, on February 7, 2012 at approximately 3:00pm onward, the following items were non-compliant, specific findings include;
A. The six sprinkler risers in the riser room are equipped with accelerator that are equipped with gate and ball valves that are not electronically supervised. West Building - Basement Sprinkler riser room
Tag No.: K0062
Based on observation, on February 7, 2012 at approximately 3:00pm onward, the following items were non-compliant, specific findings include;
A. The sprinkler head is blocked in the electrical room just off the back of the medication.
Main - 4th floor- Medication room near 4126
Tag No.: K0067
Based on observation, on February 7, 2012 at approximately 3:00pm onward, the following items were non-compliant, specific findings include;
A. The air handling unit did not shut-down with activation of duct-mounted smoke detector.
Tag No.: K0067
Based on observation, on February 7, 2012 at approximately 3:00pm onward, the following items were non-compliant, specific findings include;
A. There is no manual shutdown switch for all air handling units serving hospital based provider facilities within the medical office building.
Tag No.: K0070
Based on observation, on February 7, 2012 at approximately 3:00pm onward, the following items were non-compliant, specific findings include;
A. There are portable space heaters located in the following areas:
1. bio-med room - basement level
2. Materials supply office - basement level
Tag No.: K0072
Based on observation, on February 7, 2012 at approximately 3:00pm onward, the following items were non-compliant, specific findings include;
A. North corridor is obstructed by surgical lights and other impediments - located on ground floor of surgery center.
B. Corridor is obstructed by computer on wheels charging and stored in exit egress - located on ground floor of surgery center outside peds.
C. Exit egress to the public way is obstructed by cars in parking spaces located directly in the path of the egress. North side near parking deck.
Tag No.: K0072
Based on observation, on February 7, 2012 at approximately 3:00pm onward, the following items were non-compliant, specific findings include;
A. There are wall-mounted clerical pads that protrude into required corridor width. The pads did not self-close when opened. Pads are located between exam rooms 27 & 28 of the basement level and on 7th near the center hall employee elevators.
B. Door to bathroom protrudes greater than seven inches into required corridor width in the fully open position. Door is located between exam rooms 26 & 25 on the basement level.
C. There are impediments stored in the required egress corridor from operating rooms in the main hospital tower.
D. There are wall-mounted computers, staff identified for doctor's dictation, with filp down keyboards that protrude into required corridor width. The keyboards did not self-close when opened. Computers are located 7th and 5th floors.
Tag No.: K0075
Based on observation, on February 7, 2012 at approximately 3:00pm onward, the following items were non-compliant, specific findings include;
A. There is a large bulk soiled lined storage cart greater than 32 gallons that was stored in the changing room. Imaging Center
Tag No.: K0076
Based on observation, on February 7, 2012 at approximately 3:00pm onward, the following items were non-compliant, specific findings include;
A. The outside cylinders are not protected from extremes of weather and the cylinders are not protected from rusting while the cylinders are sitting on the concrete pad. GMH-outside- Gas manifold area
Tag No.: K0077
Based on observation, on February 7, 2012 at approximately 3:00pm onward, the following items were non-compliant, specific findings include;
A. There are oxygen and vacuum system piping supported from mechanical ducts by pipe hangers - pipe hangers must be secure to the structure - located on basement level.
Tag No.: K0078
Based on observation, on February 7, 2012 at approximately 3:00pm onward, the following items were non-compliant, specific findings include;
A. The zone control valves serving anesthetizing rooms in ENDO are not arranged to control individual rooms without shutting-off supply in other rooms. Valve box is located on the basement level.
B. The relative humidity is 32.6% and 25% respectively as measured by sensors located in operating room #7 of the main hospital tower.
Tag No.: K0141
Based on observation, on February 7, 2012 at approximately 3:00pm onward, the following items were non-compliant, specific findings include;
A. The storage room was being used for oxygen storage and there was not a No Smoking signage posted on the storage room door. Basement - Advanced Home Health Care Storage
Tag No.: K0145
Based on observation, on February 7, 2012 at approximately 3:00pm onward, the following items were non-compliant, specific findings include;
A. The emergency system supplying load indicator is not functioning on the generator annunciator panel. During loss of normal power to the Life Safety Branch transfer switch there was no visual indicator response.
Tag No.: K0145
Based on observation, on February 7, 2012 at approximately 3:00pm onward, the following items were non-compliant, specific findings include;
A. There is no emergency power system supplying load indicator for generator annunciator serving the main hospital - panels are located in the security room on the basement level.
B. There is no audible signal test switch for generator annunciator panels located within the security room - located on basement level of main hospital.
C. There is no visual indicator & audible signaling device for the low fuel level in the main fuel tank - the system is not arranged to function with a three hour fuel capacity remaining in the main fuel tanks.
Tag No.: K0147
Based on observation, on February 7, 2012 at approximately 3:00pm onward, the following items were non-compliant, specific findings include;
A. Nurse Call system and key-pad system are wired to the Life Safety Branch of the essential electrical system - located on ground floor of ambulatory surgery center.
Tag No.: K0147
Based on observation, on February 7, 2012 at approximately 3:00pm onward, the following items were non-compliant, specific findings include;
A. The circuit breaker and panelboard supplying normal power to fire alarm control panel is not identified on control panel.
Tag No.: K0147
Based on observation, on February 7, 2012 at approximately 3:00pm onward, the following items were non-compliant, specific findings include;
A. There is a broken light switch located on basement level corridor wall near female staff room on security corridor.
B. There is no bonding jumper between normal and emergency panelboards serving the same patient vicinity. Panelboards are located in electrical room " E " of the northeast tower.
Tag No.: K0211
Based on observation, on February 7, 2012 at approximately 3:00pm onward, the following items were non-compliant, specific findings include;
A. The Alcohol Based Hand Rub dispenser is within seven inches of the electrical light switch. Basement - chemical treatment area across from the nurses station.
Tag No.: K0012
Based on observation, on February 7, 2012 at approximately 3:00pm onward, the following items were non-compliant, specific findings include;
A. Smoke door labeled 20 minutes, not 45 minutes, in a one hour rated wall. Birth Center, door to triage.
Tag No.: K0012
Based on observation, on February 7, 2012 at approximately 3:00pm onward, the following items were non-compliant, specific findings include;
A. There is fire protection material missing from structural steel beams in the ROC mechanical room located on basement level.
B. There are penetrations in the ceiling around conduit and sprinkler heads that were not sealed in order to meet the required rating for the area. Basement Loading Dock Area
C. There are penetrations in the ceiling around conduit that were not sealed in order to meet the required rating for the area. 3rd floor mechanical room across from room 3202.
D. Smoke door labeled 20 minutes, not 90 minutes, in a two hour rated wall. 1st floor going into NICU classroom.
Tag No.: K0018
Based on observation, on February 7, 2012 at approximately 3:00pm onward, the following items were non-compliant, specific findings include;
A. Corridor not smoke tight with louver in door to IT room, Birth Center first floor to the right of the security desk, HUB 62.
Tag No.: K0018
Based on observation, on February 7, 2012 at approximately 3:00pm onward, the following items were non-compliant, specific findings include;
A. There are roller latches on exit access doors to imaging rooms #3, #4, and #6. Imaging rooms are located on the basement level.
B. There is no positive latching hardware on exit access doors to SCIU Suite located on the first floor of main hospital.
C. The inactive leaf of exit access doors to operating rooms require greater than a single hand motion to close and latch. The inactive leafs are equipped with manual flush bolt sets. (Located on first floor level)
Tag No.: K0018
Based on observation, on February 7, 2012 at approximately 3:00pm onward, the following items were non-compliant, specific findings include;
A. There was a gap between the double doors to the small storage room door that was not smoke resistant. Sprinkler coverage could not be obtained due to solid shelves. 4th floor Caremont Surgical Suite
Tag No.: K0020
Based on observation, on February 7, 2012 at approximately 3:00pm onward, the following items were non-compliant, specific findings include;
A. Facility at the time of the survey could not verify that the door to the Vertical Chase was a 2-hour rated door. Basement EP Storage
Tag No.: K0025
Based on observation, on February 7, 2012 at approximately 3:00pm onward, the following items were non-compliant, specific findings include;
A. There are unsealed penetrations in the 1 hour smoke barrier above the cross corridor doors at the family waiting room. Main-4th floor - cross corridor doors at the family waiting room
B. There are unsealed penetrations in the 1 hour smoke barrier above the cross corridor doors at the entrance of the PICU-S area. Main-4th floor- PICU-S
Tag No.: K0027
Based on observation, on February 7, 2012 at approximately 3:00pm onward, the following items were non-compliant, specific findings include;
A. The double doors at the smoke barrier leading into the ICU suite on the visitors entrance has a gap grater than 1/8 of an inch. Main 4th floor- ICU Visitors Entrance
Tag No.: K0029
Based on observation, on February 7, 2012 at approximately 3:00pm onward, the following items were non-compliant, specific findings include;
A. Fire doors to hyperbaric unit utilize inactive door leaf without self-closing device and automatic flush bolt assembly. (Wound Center located on third floor)
B. The roof/ceiling assembly of the hyperbaric unit utilizes a non-rated roof suspended ceiling assembly. There is no one hour fire resistive enclosure at the roof/ceiling assembly.
Tag No.: K0029
Based on observation, on February 7, 2012 at approximately 3:00pm onward, the following items were non-compliant, specific findings include;
A. The supply room, and soiled linen room are not equipped with sprinkler or one hour fire resistive enclosure. The roof ceiling assembly of each room is equipped with non-rated suspended ceiling assembly.
Tag No.: K0029
Based on observation, on February 7, 2012 at approximately 3:00pm onward, the following items were non-compliant, specific findings include;
A. The wall between the bulk storage area and pharmacy area at the double doors was not constructed to meet the one hour fire rated construction requirements for the area. Basement Bulk Storage Area
B. The maintenance closet is constructed as a two hour fire rated enclosure and is equipped with a ¾ hr rated door and is not sprinkler. Basement - Pharmacy Maintenance Closet
C. Could not verify the ¾ hour fire resistance rating of the corridor door to the Pharmacy. Basement - Pharmacy
D. The maintenance closet has two ducts penetrating the rated wall that are not equipped with fire dampers. There are holes in the wall that have not been sealed in order to meet the required fire resistance rating of the wall. Basement - Between Bulk Storage Rooms
Tag No.: K0032
Based on observation, on February 7, 2012 at approximately 3:00pm onward, the following items were non-compliant, specific findings include;
A. There is an active dead bolt installed on the patient room door, when the dead bolt is engaged it results in more than a one motion of the hand for egress from the room.
Main - 6th floor- Patient room 6156.
B. Stairway J exits into unprotected glass and steel passageway without an alternate exit from within glass and frame enclosure. The stair door prevents reentry due to access controlled egress lock assembly. The passageway encloses an interior courtyard on the basement level.
C. Stairway J is equipped with an incomplete access controlled egress lock - the exit door from the stair is not equipped with a release switch. The switch must be not greater than five feet from the door.
D. The delayed egress locks are not equipped with a sign on the door that states " Push, alarm will sound " lock will release in fifteen seconds. The locks are located near the maintenance room and triage area on the basement level.
E. Corridor area of imaging center terminates in a room with less than eight feet clear and obstructed path. The room is a waiting room located off the main corridor on the basement level.
F. There are dead-bolt locks on power operated horizontal exit doors - located on basement level near ROC waiting room.
G. The access controlled egress locks did not release during activation of the fire alarm system - Locks are located on the CT, and Imaging area cross corridor doors.
H. Exit egress door with delayed egress did not release with pull station or smoke detector. Corrected during survey. 3rd floor, peds exit stairwell.
Tag No.: K0033
Based on observation, on February 7, 2012 at approximately 3:00pm onward, the following items were non-compliant, specific findings include;
A. Fire doors to east stairway, adjacent to lobby, would not latch.
Tag No.: K0033
Based on observation, on February 7, 2012 at approximately 3:00pm onward, the following items were non-compliant, specific findings include;
A. Fire door to stair did not self latch - located on ground floor at north corridor of surgery center.
Tag No.: K0038
Based on observation, on February 7, 2012 at approximately 3:00pm onward, the following items were non-compliant, specific findings include;
A. There is a deadbolt lock in addition to other positive latching hardware on doors to CT scan #1, and #2.
Tag No.: K0040
Based on observation, on February 7, 2012 at approximately 3:00pm onward, the following items were non-compliant, specific findings include;
A. Exit access doors from restroom A is twenty-two inches in clear opening. Restroom is located in basement level imaging center.
Tag No.: K0045
Based on observation, on February 7, 2012 at approximately 3:00pm onward, the following items were non-compliant, specific findings include;
A. Exit egress lighting was switched and could leave the area in darkness. 7th floor group activities rooms, both North and South front halls.
B. Exit egress lighting was switched and could leave the area in darkness. 7th floor exam rooms, both North and South front halls.
Tag No.: K0046
Based on observation, on February 7, 2012 at approximately 3:00pm onward, the following items were non-compliant, specific findings include;
A. There is no emergency lighting for ground level exit discharge located on north side of facility.
Tag No.: K0046
Based on observation, on February 7, 2012 at approximately 3:00pm onward, the following items were non-compliant, specific findings include;
A. There is no emergency lighting to the public way for courtyard area serving the Chemo & ROC waiting area - located on basement level.
Tag No.: K0046
Based on observation, on February 7, 2012 at approximately 3:00pm onward, the following items were non-compliant, specific findings include;
A. There is no exit discharge lighting to public way - located in first floor exit passageway for north stairway.
Tag No.: K0047
Based on observation, on February 7, 2012 at approximately 3:00pm onward, the following items were non-compliant, specific findings include;
A. Additional exit and directional signs are needed in the exit corridor from the kitchen that will lead to the second mean of egress back to the stairwell. Basement Kitchen Exit Corridor
B. Additional exit and directional signs are needed in the rear exit corridor from the pharmacy. Second means of egress was not marked in the corridor. Basement - Pharmacy rear exit corridor.
C. Exit signage was not provided at exit door to the corridor. Second Floor Scan Center near Locker
Tag No.: K0047
Based on observation, on February 7, 2012 at approximately 3:00pm onward, the following items were non-compliant, specific findings include;
A. There is no exit directional signage leading from the lobby area to the mammography and MRI corridor exits. CIS- Corridors leading to mammography and MRI
Tag No.: K0056
Based on observation, on February 7, 2012 at approximately 3:00pm onward, the following items were non-compliant, specific findings include;
A. No sprinkler coverage of shower stalls in ambulatory surgery center located on the ground floor - shower stalls are located in patient rooms similar to room #3.
This item is not a deficiency per regional office and hense removed.
B. Upper and lower most portion of the stairwell landing not sprinklered in the north stairwell MOB.
Tag No.: K0056
Based on observation, on February 7, 2012 at approximately 3:00pm onward, the following items were non-compliant, specific findings include;
A. The closet has a sprinkler head that is rated 200 degree F intermediate temperature rating in place of 155 degree F ordinary temperature rating. Second floor data closet near medical records passage way
B. The vertical shaft was not equipped sprinkler protection. A, B, C, D, E, F, G and H Vertical Mechanical Chase
C. The sprinkler system was blocked by a solid shower curtain in rooms 7105 and 7252. 7th floor
Tag No.: K0061
Based on observation, on February 7, 2012 at approximately 3:00pm onward, the following items were non-compliant, specific findings include;
A. The six sprinkler risers in the riser room are equipped with accelerator that are equipped with gate and ball valves that are not electronically supervised. West Building - Basement Sprinkler riser room
Tag No.: K0062
Based on observation, on February 7, 2012 at approximately 3:00pm onward, the following items were non-compliant, specific findings include;
A. The sprinkler head is blocked in the electrical room just off the back of the medication.
Main - 4th floor- Medication room near 4126
Tag No.: K0067
Based on observation, on February 7, 2012 at approximately 3:00pm onward, the following items were non-compliant, specific findings include;
A. The air handling unit did not shut-down with activation of duct-mounted smoke detector.
Tag No.: K0067
Based on observation, on February 7, 2012 at approximately 3:00pm onward, the following items were non-compliant, specific findings include;
A. There is no manual shutdown switch for all air handling units serving hospital based provider facilities within the medical office building.
Tag No.: K0070
Based on observation, on February 7, 2012 at approximately 3:00pm onward, the following items were non-compliant, specific findings include;
A. There are portable space heaters located in the following areas:
1. bio-med room - basement level
2. Materials supply office - basement level
Tag No.: K0072
Based on observation, on February 7, 2012 at approximately 3:00pm onward, the following items were non-compliant, specific findings include;
A. North corridor is obstructed by surgical lights and other impediments - located on ground floor of surgery center.
B. Corridor is obstructed by computer on wheels charging and stored in exit egress - located on ground floor of surgery center outside peds.
C. Exit egress to the public way is obstructed by cars in parking spaces located directly in the path of the egress. North side near parking deck.
Tag No.: K0072
Based on observation, on February 7, 2012 at approximately 3:00pm onward, the following items were non-compliant, specific findings include;
A. There are wall-mounted clerical pads that protrude into required corridor width. The pads did not self-close when opened. Pads are located between exam rooms 27 & 28 of the basement level and on 7th near the center hall employee elevators.
B. Door to bathroom protrudes greater than seven inches into required corridor width in the fully open position. Door is located between exam rooms 26 & 25 on the basement level.
C. There are impediments stored in the required egress corridor from operating rooms in the main hospital tower.
D. There are wall-mounted computers, staff identified for doctor's dictation, with filp down keyboards that protrude into required corridor width. The keyboards did not self-close when opened. Computers are located 7th and 5th floors.
Tag No.: K0075
Based on observation, on February 7, 2012 at approximately 3:00pm onward, the following items were non-compliant, specific findings include;
A. There is a large bulk soiled lined storage cart greater than 32 gallons that was stored in the changing room. Imaging Center
Tag No.: K0076
Based on observation, on February 7, 2012 at approximately 3:00pm onward, the following items were non-compliant, specific findings include;
A. The outside cylinders are not protected from extremes of weather and the cylinders are not protected from rusting while the cylinders are sitting on the concrete pad. GMH-outside- Gas manifold area
Tag No.: K0077
Based on observation, on February 7, 2012 at approximately 3:00pm onward, the following items were non-compliant, specific findings include;
A. There are oxygen and vacuum system piping supported from mechanical ducts by pipe hangers - pipe hangers must be secure to the structure - located on basement level.
Tag No.: K0078
Based on observation, on February 7, 2012 at approximately 3:00pm onward, the following items were non-compliant, specific findings include;
A. The zone control valves serving anesthetizing rooms in ENDO are not arranged to control individual rooms without shutting-off supply in other rooms. Valve box is located on the basement level.
B. The relative humidity is 32.6% and 25% respectively as measured by sensors located in operating room #7 of the main hospital tower.
Tag No.: K0141
Based on observation, on February 7, 2012 at approximately 3:00pm onward, the following items were non-compliant, specific findings include;
A. The storage room was being used for oxygen storage and there was not a No Smoking signage posted on the storage room door. Basement - Advanced Home Health Care Storage
Tag No.: K0145
Based on observation, on February 7, 2012 at approximately 3:00pm onward, the following items were non-compliant, specific findings include;
A. The emergency system supplying load indicator is not functioning on the generator annunciator panel. During loss of normal power to the Life Safety Branch transfer switch there was no visual indicator response.
Tag No.: K0145
Based on observation, on February 7, 2012 at approximately 3:00pm onward, the following items were non-compliant, specific findings include;
A. There is no emergency power system supplying load indicator for generator annunciator serving the main hospital - panels are located in the security room on the basement level.
B. There is no audible signal test switch for generator annunciator panels located within the security room - located on basement level of main hospital.
C. There is no visual indicator & audible signaling device for the low fuel level in the main fuel tank - the system is not arranged to function with a three hour fuel capacity remaining in the main fuel tanks.
Tag No.: K0147
Based on observation, on February 7, 2012 at approximately 3:00pm onward, the following items were non-compliant, specific findings include;
A. Nurse Call system and key-pad system are wired to the Life Safety Branch of the essential electrical system - located on ground floor of ambulatory surgery center.
Tag No.: K0147
Based on observation, on February 7, 2012 at approximately 3:00pm onward, the following items were non-compliant, specific findings include;
A. The circuit breaker and panelboard supplying normal power to fire alarm control panel is not identified on control panel.
Tag No.: K0147
Based on observation, on February 7, 2012 at approximately 3:00pm onward, the following items were non-compliant, specific findings include;
A. There is a broken light switch located on basement level corridor wall near female staff room on security corridor.
B. There is no bonding jumper between normal and emergency panelboards serving the same patient vicinity. Panelboards are located in electrical room " E " of the northeast tower.