Tag No.: K0012

Based on observation, on February 7, 2012 at approximately 3:00pm onward, the following items were non-compliant, specific findings include;

A. Smoke door labeled 20 minutes, not 45 minutes, in a one hour rated wall. Birth Center, door to triage.

No Description Available

Tag No.: K0012

Based on observation, on February 7, 2012 at approximately 3:00pm onward, the following items were non-compliant, specific findings include;

A. There is fire protection material missing from structural steel beams in the ROC mechanical room located on basement level.

B. There are penetrations in the ceiling around conduit and sprinkler heads that were not sealed in order to meet the required rating for the area. Basement Loading Dock Area

C. There are penetrations in the ceiling around conduit that were not sealed in order to meet the required rating for the area. 3rd floor mechanical room across from room 3202.

D. Smoke door labeled 20 minutes, not 90 minutes, in a two hour rated wall. 1st floor going into NICU classroom.

No Description Available

Tag No.: K0018

Based on observation, on February 7, 2012 at approximately 3:00pm onward, the following items were non-compliant, specific findings include;

A. Corridor not smoke tight with louver in door to IT room, Birth Center first floor to the right of the security desk, HUB 62.

No Description Available

Tag No.: K0018

Based on observation, on February 7, 2012 at approximately 3:00pm onward, the following items were non-compliant, specific findings include;

A. There are roller latches on exit access doors to imaging rooms #3, #4, and #6. Imaging rooms are located on the basement level.

B. There is no positive latching hardware on exit access doors to SCIU Suite located on the first floor of main hospital.

C. The inactive leaf of exit access doors to operating rooms require greater than a single hand motion to close and latch. The inactive leafs are equipped with manual flush bolt sets. (Located on first floor level)

No Description Available

Tag No.: K0018

Based on observation, on February 7, 2012 at approximately 3:00pm onward, the following items were non-compliant, specific findings include;

A. There was a gap between the double doors to the small storage room door that was not smoke resistant. Sprinkler coverage could not be obtained due to solid shelves. 4th floor Caremont Surgical Suite

No Description Available

Tag No.: K0020

Based on observation, on February 7, 2012 at approximately 3:00pm onward, the following items were non-compliant, specific findings include;

A. Facility at the time of the survey could not verify that the door to the Vertical Chase was a 2-hour rated door. Basement EP Storage

No Description Available

Tag No.: K0025

Based on observation, on February 7, 2012 at approximately 3:00pm onward, the following items were non-compliant, specific findings include;

A. There are unsealed penetrations in the 1 hour smoke barrier above the cross corridor doors at the family waiting room. Main-4th floor - cross corridor doors at the family waiting room

B. There are unsealed penetrations in the 1 hour smoke barrier above the cross corridor doors at the entrance of the PICU-S area. Main-4th floor- PICU-S

No Description Available

Tag No.: K0027

Based on observation, on February 7, 2012 at approximately 3:00pm onward, the following items were non-compliant, specific findings include;

A. The double doors at the smoke barrier leading into the ICU suite on the visitors entrance has a gap grater than 1/8 of an inch. Main 4th floor- ICU Visitors Entrance

No Description Available

Tag No.: K0029

Based on observation, on February 7, 2012 at approximately 3:00pm onward, the following items were non-compliant, specific findings include;

A. Fire doors to hyperbaric unit utilize inactive door leaf without self-closing device and automatic flush bolt assembly. (Wound Center located on third floor)

B. The roof/ceiling assembly of the hyperbaric unit utilizes a non-rated roof suspended ceiling assembly. There is no one hour fire resistive enclosure at the roof/ceiling assembly.

No Description Available

Tag No.: K0029

Based on observation, on February 7, 2012 at approximately 3:00pm onward, the following items were non-compliant, specific findings include;

A. The supply room, and soiled linen room are not equipped with sprinkler or one hour fire resistive enclosure. The roof ceiling assembly of each room is equipped with non-rated suspended ceiling assembly.

No Description Available

Tag No.: K0029

Based on observation, on February 7, 2012 at approximately 3:00pm onward, the following items were non-compliant, specific findings include;

A. The wall between the bulk storage area and pharmacy area at the double doors was not constructed to meet the one hour fire rated construction requirements for the area. Basement Bulk Storage Area

B. The maintenance closet is constructed as a two hour fire rated enclosure and is equipped with a ¾ hr rated door and is not sprinkler. Basement - Pharmacy Maintenance Closet

C. Could not verify the ¾ hour fire resistance rating of the corridor door to the Pharmacy. Basement - Pharmacy

D. The maintenance closet has two ducts penetrating the rated wall that are not equipped with fire dampers. There are holes in the wall that have not been sealed in order to meet the required fire resistance rating of the wall. Basement - Between Bulk Storage Rooms

No Description Available

Tag No.: K0032

Based on observation, on February 7, 2012 at approximately 3:00pm onward, the following items were non-compliant, specific findings include;

A. There is an active dead bolt installed on the patient room door, when the dead bolt is engaged it results in more than a one motion of the hand for egress from the room.
Main - 6th floor- Patient room 6156.

B. Stairway J exits into unprotected glass and steel passageway without an alternate exit from within glass and frame enclosure. The stair door prevents reentry due to access controlled egress lock assembly. The passageway encloses an interior courtyard on the basement level.

C. Stairway J is equipped with an incomplete access controlled egress lock - the exit door from the stair is not equipped with a release switch. The switch must be not greater than five feet from the door.

D. The delayed egress locks are not equipped with a sign on the door that states " Push, alarm will sound " lock will release in fifteen seconds. The locks are located near the maintenance room and triage area on the basement level.

E. Corridor area of imaging center terminates in a room with less than eight feet clear and obstructed path. The room is a waiting room located off the main corridor on the basement level.

F. There are dead-bolt locks on power operated horizontal exit doors - located on basement level near ROC waiting room.

G. The access controlled egress locks did not release during activation of the fire alarm system - Locks are located on the CT, and Imaging area cross corridor doors.

H. Exit egress door with delayed egress did not release with pull station or smoke detector. Corrected during survey. 3rd floor, peds exit stairwell.

No Description Available

Tag No.: K0033

Based on observation, on February 7, 2012 at approximately 3:00pm onward, the following items were non-compliant, specific findings include;

A. Fire doors to east stairway, adjacent to lobby, would not latch.

No Description Available

Tag No.: K0033

Based on observation, on February 7, 2012 at approximately 3:00pm onward, the following items were non-compliant, specific findings include;

A. Fire door to stair did not self latch - located on ground floor at north corridor of surgery center.

No Description Available

Tag No.: K0038

Based on observation, on February 7, 2012 at approximately 3:00pm onward, the following items were non-compliant, specific findings include;

A. There is a deadbolt lock in addition to other positive latching hardware on doors to CT scan #1, and #2.

No Description Available

Tag No.: K0040

Based on observation, on February 7, 2012 at approximately 3:00pm onward, the following items were non-compliant, specific findings include;

A. Exit access doors from restroom A is twenty-two inches in clear opening. Restroom is located in basement level imaging center.

No Description Available

Tag No.: K0045

Based on observation, on February 7, 2012 at approximately 3:00pm onward, the following items were non-compliant, specific findings include;

A. Exit egress lighting was switched and could leave the area in darkness. 7th floor group activities rooms, both North and South front halls.

B. Exit egress lighting was switched and could leave the area in darkness. 7th floor exam rooms, both North and South front halls.

No Description Available

Tag No.: K0046

Based on observation, on February 7, 2012 at approximately 3:00pm onward, the following items were non-compliant, specific findings include;

A. There is no emergency lighting for ground level exit discharge located on north side of facility.

No Description Available

Tag No.: K0046

Based on observation, on February 7, 2012 at approximately 3:00pm onward, the following items were non-compliant, specific findings include;

A. There is no emergency lighting to the public way for courtyard area serving the Chemo & ROC waiting area - located on basement level.

No Description Available

Tag No.: K0046

Based on observation, on February 7, 2012 at approximately 3:00pm onward, the following items were non-compliant, specific findings include;

A. There is no exit discharge lighting to public way - located in first floor exit passageway for north stairway.

No Description Available

Tag No.: K0047

Based on observation, on February 7, 2012 at approximately 3:00pm onward, the following items were non-compliant, specific findings include;

A. Additional exit and directional signs are needed in the exit corridor from the kitchen that will lead to the second mean of egress back to the stairwell. Basement Kitchen Exit Corridor

B. Additional exit and directional signs are needed in the rear exit corridor from the pharmacy. Second means of egress was not marked in the corridor. Basement - Pharmacy rear exit corridor.

C. Exit signage was not provided at exit door to the corridor. Second Floor Scan Center near Locker

No Description Available

Tag No.: K0047

Based on observation, on February 7, 2012 at approximately 3:00pm onward, the following items were non-compliant, specific findings include;

A. There is no exit directional signage leading from the lobby area to the mammography and MRI corridor exits. CIS- Corridors leading to mammography and MRI

No Description Available

Tag No.: K0056

Based on observation, on February 7, 2012 at approximately 3:00pm onward, the following items were non-compliant, specific findings include;

A. No sprinkler coverage of shower stalls in ambulatory surgery center located on the ground floor - shower stalls are located in patient rooms similar to room #3.

This item is not a deficiency per regional office and hense removed.

B. Upper and lower most portion of the stairwell landing not sprinklered in the north stairwell MOB.

No Description Available

Tag No.: K0056

Based on observation, on February 7, 2012 at approximately 3:00pm onward, the following items were non-compliant, specific findings include;

A. The closet has a sprinkler head that is rated 200 degree F intermediate temperature rating in place of 155 degree F ordinary temperature rating. Second floor data closet near medical records passage way

B. The vertical shaft was not equipped sprinkler protection. A, B, C, D, E, F, G and H Vertical Mechanical Chase

C. The sprinkler system was blocked by a solid shower curtain in rooms 7105 and 7252. 7th floor

No Description Available

Tag No.: K0061

Based on observation, on February 7, 2012 at approximately 3:00pm onward, the following items were non-compliant, specific findings include;

A. The six sprinkler risers in the riser room are equipped with accelerator that are equipped with gate and ball valves that are not electronically supervised. West Building - Basement Sprinkler riser room

No Description Available

Tag No.: K0062

Based on observation, on February 7, 2012 at approximately 3:00pm onward, the following items were non-compliant, specific findings include;

A. The sprinkler head is blocked in the electrical room just off the back of the medication.
Main - 4th floor- Medication room near 4126

No Description Available

Tag No.: K0067

Based on observation, on February 7, 2012 at approximately 3:00pm onward, the following items were non-compliant, specific findings include;

A. The air handling unit did not shut-down with activation of duct-mounted smoke detector.

No Description Available

Tag No.: K0067

Based on observation, on February 7, 2012 at approximately 3:00pm onward, the following items were non-compliant, specific findings include;

A. There is no manual shutdown switch for all air handling units serving hospital based provider facilities within the medical office building.

No Description Available

Tag No.: K0070

Based on observation, on February 7, 2012 at approximately 3:00pm onward, the following items were non-compliant, specific findings include;

A. There are portable space heaters located in the following areas:

1. bio-med room - basement level

2. Materials supply office - basement level

No Description Available

Tag No.: K0072

Based on observation, on February 7, 2012 at approximately 3:00pm onward, the following items were non-compliant, specific findings include;

A. North corridor is obstructed by surgical lights and other impediments - located on ground floor of surgery center.

B. Corridor is obstructed by computer on wheels charging and stored in exit egress - located on ground floor of surgery center outside peds.

C. Exit egress to the public way is obstructed by cars in parking spaces located directly in the path of the egress. North side near parking deck.

No Description Available

Tag No.: K0072

Based on observation, on February 7, 2012 at approximately 3:00pm onward, the following items were non-compliant, specific findings include;

A. There are wall-mounted clerical pads that protrude into required corridor width. The pads did not self-close when opened. Pads are located between exam rooms 27 & 28 of the basement level and on 7th near the center hall employee elevators.

B. Door to bathroom protrudes greater than seven inches into required corridor width in the fully open position. Door is located between exam rooms 26 & 25 on the basement level.

C. There are impediments stored in the required egress corridor from operating rooms in the main hospital tower.

D. There are wall-mounted computers, staff identified for doctor's dictation, with filp down keyboards that protrude into required corridor width. The keyboards did not self-close when opened. Computers are located 7th and 5th floors.

No Description Available

Tag No.: K0075

Based on observation, on February 7, 2012 at approximately 3:00pm onward, the following items were non-compliant, specific findings include;

A. There is a large bulk soiled lined storage cart greater than 32 gallons that was stored in the changing room. Imaging Center

No Description Available

Tag No.: K0076

Based on observation, on February 7, 2012 at approximately 3:00pm onward, the following items were non-compliant, specific findings include;

A. The outside cylinders are not protected from extremes of weather and the cylinders are not protected from rusting while the cylinders are sitting on the concrete pad. GMH-outside- Gas manifold area

No Description Available

Tag No.: K0077

Based on observation, on February 7, 2012 at approximately 3:00pm onward, the following items were non-compliant, specific findings include;

A. There are oxygen and vacuum system piping supported from mechanical ducts by pipe hangers - pipe hangers must be secure to the structure - located on basement level.

No Description Available

Tag No.: K0078

Based on observation, on February 7, 2012 at approximately 3:00pm onward, the following items were non-compliant, specific findings include;

A. The zone control valves serving anesthetizing rooms in ENDO are not arranged to control individual rooms without shutting-off supply in other rooms. Valve box is located on the basement level.

B. The relative humidity is 32.6% and 25% respectively as measured by sensors located in operating room #7 of the main hospital tower.

No Description Available

Tag No.: K0141

Based on observation, on February 7, 2012 at approximately 3:00pm onward, the following items were non-compliant, specific findings include;

A. The storage room was being used for oxygen storage and there was not a No Smoking signage posted on the storage room door. Basement - Advanced Home Health Care Storage

No Description Available

Tag No.: K0145

Based on observation, on February 7, 2012 at approximately 3:00pm onward, the following items were non-compliant, specific findings include;

A. The emergency system supplying load indicator is not functioning on the generator annunciator panel. During loss of normal power to the Life Safety Branch transfer switch there was no visual indicator response.

No Description Available

Tag No.: K0145

Based on observation, on February 7, 2012 at approximately 3:00pm onward, the following items were non-compliant, specific findings include;

A. There is no emergency power system supplying load indicator for generator annunciator serving the main hospital - panels are located in the security room on the basement level.

B. There is no audible signal test switch for generator annunciator panels located within the security room - located on basement level of main hospital.

C. There is no visual indicator & audible signaling device for the low fuel level in the main fuel tank - the system is not arranged to function with a three hour fuel capacity remaining in the main fuel tanks.

No Description Available

Tag No.: K0147

Based on observation, on February 7, 2012 at approximately 3:00pm onward, the following items were non-compliant, specific findings include;

A. Nurse Call system and key-pad system are wired to the Life Safety Branch of the essential electrical system - located on ground floor of ambulatory surgery center.

No Description Available

Tag No.: K0147

Based on observation, on February 7, 2012 at approximately 3:00pm onward, the following items were non-compliant, specific findings include;

A. The circuit breaker and panelboard supplying normal power to fire alarm control panel is not identified on control panel.

No Description Available

Tag No.: K0147

Based on observation, on February 7, 2012 at approximately 3:00pm onward, the following items were non-compliant, specific findings include;

A. There is a broken light switch located on basement level corridor wall near female staff room on security corridor.

B. There is no bonding jumper between normal and emergency panelboards serving the same patient vicinity. Panelboards are located in electrical room " E " of the northeast tower.

Means of Egress - General

Tag No.: K0211

Based on observation, on February 7, 2012 at approximately 3:00pm onward, the following items were non-compliant, specific findings include;

A. The Alcohol Based Hand Rub dispenser is within seven inches of the electrical light switch. Basement - chemical treatment area across from the nurses station.

LIFE SAFETY CODE STANDARD

Tag No.: K0012

Based on observation, on February 7, 2012 at approximately 3:00pm onward, the following items were non-compliant, specific findings include;

A. Smoke door labeled 20 minutes, not 45 minutes, in a one hour rated wall. Birth Center, door to triage.

LIFE SAFETY CODE STANDARD

Tag No.: K0012

Based on observation, on February 7, 2012 at approximately 3:00pm onward, the following items were non-compliant, specific findings include;

A. There is fire protection material missing from structural steel beams in the ROC mechanical room located on basement level.

B. There are penetrations in the ceiling around conduit and sprinkler heads that were not sealed in order to meet the required rating for the area. Basement Loading Dock Area

C. There are penetrations in the ceiling around conduit that were not sealed in order to meet the required rating for the area. 3rd floor mechanical room across from room 3202.

D. Smoke door labeled 20 minutes, not 90 minutes, in a two hour rated wall. 1st floor going into NICU classroom.

LIFE SAFETY CODE STANDARD

Tag No.: K0018

Based on observation, on February 7, 2012 at approximately 3:00pm onward, the following items were non-compliant, specific findings include;

A. Corridor not smoke tight with louver in door to IT room, Birth Center first floor to the right of the security desk, HUB 62.

LIFE SAFETY CODE STANDARD

Tag No.: K0018

Based on observation, on February 7, 2012 at approximately 3:00pm onward, the following items were non-compliant, specific findings include;

A. There are roller latches on exit access doors to imaging rooms #3, #4, and #6. Imaging rooms are located on the basement level.

B. There is no positive latching hardware on exit access doors to SCIU Suite located on the first floor of main hospital.

C. The inactive leaf of exit access doors to operating rooms require greater than a single hand motion to close and latch. The inactive leafs are equipped with manual flush bolt sets. (Located on first floor level)

LIFE SAFETY CODE STANDARD

Tag No.: K0018

Based on observation, on February 7, 2012 at approximately 3:00pm onward, the following items were non-compliant, specific findings include;

A. There was a gap between the double doors to the small storage room door that was not smoke resistant. Sprinkler coverage could not be obtained due to solid shelves. 4th floor Caremont Surgical Suite

LIFE SAFETY CODE STANDARD

Tag No.: K0020

Based on observation, on February 7, 2012 at approximately 3:00pm onward, the following items were non-compliant, specific findings include;

A. Facility at the time of the survey could not verify that the door to the Vertical Chase was a 2-hour rated door. Basement EP Storage

LIFE SAFETY CODE STANDARD

Tag No.: K0025

Based on observation, on February 7, 2012 at approximately 3:00pm onward, the following items were non-compliant, specific findings include;

A. There are unsealed penetrations in the 1 hour smoke barrier above the cross corridor doors at the family waiting room. Main-4th floor - cross corridor doors at the family waiting room

B. There are unsealed penetrations in the 1 hour smoke barrier above the cross corridor doors at the entrance of the PICU-S area. Main-4th floor- PICU-S

LIFE SAFETY CODE STANDARD

Tag No.: K0027

Based on observation, on February 7, 2012 at approximately 3:00pm onward, the following items were non-compliant, specific findings include;

A. The double doors at the smoke barrier leading into the ICU suite on the visitors entrance has a gap grater than 1/8 of an inch. Main 4th floor- ICU Visitors Entrance

LIFE SAFETY CODE STANDARD

Tag No.: K0029

Based on observation, on February 7, 2012 at approximately 3:00pm onward, the following items were non-compliant, specific findings include;

A. Fire doors to hyperbaric unit utilize inactive door leaf without self-closing device and automatic flush bolt assembly. (Wound Center located on third floor)

B. The roof/ceiling assembly of the hyperbaric unit utilizes a non-rated roof suspended ceiling assembly. There is no one hour fire resistive enclosure at the roof/ceiling assembly.

LIFE SAFETY CODE STANDARD

Tag No.: K0029

Based on observation, on February 7, 2012 at approximately 3:00pm onward, the following items were non-compliant, specific findings include;

A. The supply room, and soiled linen room are not equipped with sprinkler or one hour fire resistive enclosure. The roof ceiling assembly of each room is equipped with non-rated suspended ceiling assembly.

LIFE SAFETY CODE STANDARD

Tag No.: K0029

Based on observation, on February 7, 2012 at approximately 3:00pm onward, the following items were non-compliant, specific findings include;

A. The wall between the bulk storage area and pharmacy area at the double doors was not constructed to meet the one hour fire rated construction requirements for the area. Basement Bulk Storage Area

B. The maintenance closet is constructed as a two hour fire rated enclosure and is equipped with a ¾ hr rated door and is not sprinkler. Basement - Pharmacy Maintenance Closet

C. Could not verify the ¾ hour fire resistance rating of the corridor door to the Pharmacy. Basement - Pharmacy

D. The maintenance closet has two ducts penetrating the rated wall that are not equipped with fire dampers. There are holes in the wall that have not been sealed in order to meet the required fire resistance rating of the wall. Basement - Between Bulk Storage Rooms

LIFE SAFETY CODE STANDARD

Tag No.: K0032

Based on observation, on February 7, 2012 at approximately 3:00pm onward, the following items were non-compliant, specific findings include;

A. There is an active dead bolt installed on the patient room door, when the dead bolt is engaged it results in more than a one motion of the hand for egress from the room.
Main - 6th floor- Patient room 6156.

B. Stairway J exits into unprotected glass and steel passageway without an alternate exit from within glass and frame enclosure. The stair door prevents reentry due to access controlled egress lock assembly. The passageway encloses an interior courtyard on the basement level.

C. Stairway J is equipped with an incomplete access controlled egress lock - the exit door from the stair is not equipped with a release switch. The switch must be not greater than five feet from the door.

D. The delayed egress locks are not equipped with a sign on the door that states " Push, alarm will sound " lock will release in fifteen seconds. The locks are located near the maintenance room and triage area on the basement level.

E. Corridor area of imaging center terminates in a room with less than eight feet clear and obstructed path. The room is a waiting room located off the main corridor on the basement level.

F. There are dead-bolt locks on power operated horizontal exit doors - located on basement level near ROC waiting room.

G. The access controlled egress locks did not release during activation of the fire alarm system - Locks are located on the CT, and Imaging area cross corridor doors.

H. Exit egress door with delayed egress did not release with pull station or smoke detector. Corrected during survey. 3rd floor, peds exit stairwell.

LIFE SAFETY CODE STANDARD

Tag No.: K0033

Based on observation, on February 7, 2012 at approximately 3:00pm onward, the following items were non-compliant, specific findings include;

A. Fire doors to east stairway, adjacent to lobby, would not latch.

LIFE SAFETY CODE STANDARD

Tag No.: K0033

Based on observation, on February 7, 2012 at approximately 3:00pm onward, the following items were non-compliant, specific findings include;

A. Fire door to stair did not self latch - located on ground floor at north corridor of surgery center.

LIFE SAFETY CODE STANDARD

Tag No.: K0038

Based on observation, on February 7, 2012 at approximately 3:00pm onward, the following items were non-compliant, specific findings include;

A. There is a deadbolt lock in addition to other positive latching hardware on doors to CT scan #1, and #2.

LIFE SAFETY CODE STANDARD

Tag No.: K0040

Based on observation, on February 7, 2012 at approximately 3:00pm onward, the following items were non-compliant, specific findings include;

A. Exit access doors from restroom A is twenty-two inches in clear opening. Restroom is located in basement level imaging center.

LIFE SAFETY CODE STANDARD

Tag No.: K0045

Based on observation, on February 7, 2012 at approximately 3:00pm onward, the following items were non-compliant, specific findings include;

A. Exit egress lighting was switched and could leave the area in darkness. 7th floor group activities rooms, both North and South front halls.

B. Exit egress lighting was switched and could leave the area in darkness. 7th floor exam rooms, both North and South front halls.

LIFE SAFETY CODE STANDARD

Tag No.: K0046

Based on observation, on February 7, 2012 at approximately 3:00pm onward, the following items were non-compliant, specific findings include;

A. There is no emergency lighting for ground level exit discharge located on north side of facility.

LIFE SAFETY CODE STANDARD

Tag No.: K0046

Based on observation, on February 7, 2012 at approximately 3:00pm onward, the following items were non-compliant, specific findings include;

A. There is no emergency lighting to the public way for courtyard area serving the Chemo & ROC waiting area - located on basement level.

LIFE SAFETY CODE STANDARD

Tag No.: K0046

Based on observation, on February 7, 2012 at approximately 3:00pm onward, the following items were non-compliant, specific findings include;

A. There is no exit discharge lighting to public way - located in first floor exit passageway for north stairway.

LIFE SAFETY CODE STANDARD

Tag No.: K0047

Based on observation, on February 7, 2012 at approximately 3:00pm onward, the following items were non-compliant, specific findings include;

A. Additional exit and directional signs are needed in the exit corridor from the kitchen that will lead to the second mean of egress back to the stairwell. Basement Kitchen Exit Corridor

B. Additional exit and directional signs are needed in the rear exit corridor from the pharmacy. Second means of egress was not marked in the corridor. Basement - Pharmacy rear exit corridor.

C. Exit signage was not provided at exit door to the corridor. Second Floor Scan Center near Locker

LIFE SAFETY CODE STANDARD

Tag No.: K0047

Based on observation, on February 7, 2012 at approximately 3:00pm onward, the following items were non-compliant, specific findings include;

A. There is no exit directional signage leading from the lobby area to the mammography and MRI corridor exits. CIS- Corridors leading to mammography and MRI

LIFE SAFETY CODE STANDARD

Tag No.: K0056

Based on observation, on February 7, 2012 at approximately 3:00pm onward, the following items were non-compliant, specific findings include;

A. No sprinkler coverage of shower stalls in ambulatory surgery center located on the ground floor - shower stalls are located in patient rooms similar to room #3.

This item is not a deficiency per regional office and hense removed.

B. Upper and lower most portion of the stairwell landing not sprinklered in the north stairwell MOB.

LIFE SAFETY CODE STANDARD

Tag No.: K0056

Based on observation, on February 7, 2012 at approximately 3:00pm onward, the following items were non-compliant, specific findings include;

A. The closet has a sprinkler head that is rated 200 degree F intermediate temperature rating in place of 155 degree F ordinary temperature rating. Second floor data closet near medical records passage way

B. The vertical shaft was not equipped sprinkler protection. A, B, C, D, E, F, G and H Vertical Mechanical Chase

C. The sprinkler system was blocked by a solid shower curtain in rooms 7105 and 7252. 7th floor

LIFE SAFETY CODE STANDARD

Tag No.: K0061

Based on observation, on February 7, 2012 at approximately 3:00pm onward, the following items were non-compliant, specific findings include;

A. The six sprinkler risers in the riser room are equipped with accelerator that are equipped with gate and ball valves that are not electronically supervised. West Building - Basement Sprinkler riser room

LIFE SAFETY CODE STANDARD

Tag No.: K0062

Based on observation, on February 7, 2012 at approximately 3:00pm onward, the following items were non-compliant, specific findings include;

A. The sprinkler head is blocked in the electrical room just off the back of the medication.
Main - 4th floor- Medication room near 4126

LIFE SAFETY CODE STANDARD

Tag No.: K0067

Based on observation, on February 7, 2012 at approximately 3:00pm onward, the following items were non-compliant, specific findings include;

A. The air handling unit did not shut-down with activation of duct-mounted smoke detector.

LIFE SAFETY CODE STANDARD

Tag No.: K0067

Based on observation, on February 7, 2012 at approximately 3:00pm onward, the following items were non-compliant, specific findings include;

A. There is no manual shutdown switch for all air handling units serving hospital based provider facilities within the medical office building.

LIFE SAFETY CODE STANDARD

Tag No.: K0070

Based on observation, on February 7, 2012 at approximately 3:00pm onward, the following items were non-compliant, specific findings include;

A. There are portable space heaters located in the following areas:

1. bio-med room - basement level

2. Materials supply office - basement level

LIFE SAFETY CODE STANDARD

Tag No.: K0072

Based on observation, on February 7, 2012 at approximately 3:00pm onward, the following items were non-compliant, specific findings include;

A. North corridor is obstructed by surgical lights and other impediments - located on ground floor of surgery center.

B. Corridor is obstructed by computer on wheels charging and stored in exit egress - located on ground floor of surgery center outside peds.

C. Exit egress to the public way is obstructed by cars in parking spaces located directly in the path of the egress. North side near parking deck.

LIFE SAFETY CODE STANDARD

Tag No.: K0072

Based on observation, on February 7, 2012 at approximately 3:00pm onward, the following items were non-compliant, specific findings include;

A. There are wall-mounted clerical pads that protrude into required corridor width. The pads did not self-close when opened. Pads are located between exam rooms 27 & 28 of the basement level and on 7th near the center hall employee elevators.

B. Door to bathroom protrudes greater than seven inches into required corridor width in the fully open position. Door is located between exam rooms 26 & 25 on the basement level.

C. There are impediments stored in the required egress corridor from operating rooms in the main hospital tower.

D. There are wall-mounted computers, staff identified for doctor's dictation, with filp down keyboards that protrude into required corridor width. The keyboards did not self-close when opened. Computers are located 7th and 5th floors.

LIFE SAFETY CODE STANDARD

Tag No.: K0075

Based on observation, on February 7, 2012 at approximately 3:00pm onward, the following items were non-compliant, specific findings include;

A. There is a large bulk soiled lined storage cart greater than 32 gallons that was stored in the changing room. Imaging Center

LIFE SAFETY CODE STANDARD

Tag No.: K0076

Based on observation, on February 7, 2012 at approximately 3:00pm onward, the following items were non-compliant, specific findings include;

A. The outside cylinders are not protected from extremes of weather and the cylinders are not protected from rusting while the cylinders are sitting on the concrete pad. GMH-outside- Gas manifold area

LIFE SAFETY CODE STANDARD

Tag No.: K0077

Based on observation, on February 7, 2012 at approximately 3:00pm onward, the following items were non-compliant, specific findings include;

A. There are oxygen and vacuum system piping supported from mechanical ducts by pipe hangers - pipe hangers must be secure to the structure - located on basement level.

LIFE SAFETY CODE STANDARD

Tag No.: K0078

Based on observation, on February 7, 2012 at approximately 3:00pm onward, the following items were non-compliant, specific findings include;

A. The zone control valves serving anesthetizing rooms in ENDO are not arranged to control individual rooms without shutting-off supply in other rooms. Valve box is located on the basement level.

B. The relative humidity is 32.6% and 25% respectively as measured by sensors located in operating room #7 of the main hospital tower.

LIFE SAFETY CODE STANDARD

Tag No.: K0141

Based on observation, on February 7, 2012 at approximately 3:00pm onward, the following items were non-compliant, specific findings include;

A. The storage room was being used for oxygen storage and there was not a No Smoking signage posted on the storage room door. Basement - Advanced Home Health Care Storage

LIFE SAFETY CODE STANDARD

Tag No.: K0145

Based on observation, on February 7, 2012 at approximately 3:00pm onward, the following items were non-compliant, specific findings include;

A. The emergency system supplying load indicator is not functioning on the generator annunciator panel. During loss of normal power to the Life Safety Branch transfer switch there was no visual indicator response.

LIFE SAFETY CODE STANDARD

Tag No.: K0145

Based on observation, on February 7, 2012 at approximately 3:00pm onward, the following items were non-compliant, specific findings include;

A. There is no emergency power system supplying load indicator for generator annunciator serving the main hospital - panels are located in the security room on the basement level.

B. There is no audible signal test switch for generator annunciator panels located within the security room - located on basement level of main hospital.

C. There is no visual indicator & audible signaling device for the low fuel level in the main fuel tank - the system is not arranged to function with a three hour fuel capacity remaining in the main fuel tanks.

LIFE SAFETY CODE STANDARD

Tag No.: K0147

Based on observation, on February 7, 2012 at approximately 3:00pm onward, the following items were non-compliant, specific findings include;

A. Nurse Call system and key-pad system are wired to the Life Safety Branch of the essential electrical system - located on ground floor of ambulatory surgery center.

LIFE SAFETY CODE STANDARD

Tag No.: K0147

Based on observation, on February 7, 2012 at approximately 3:00pm onward, the following items were non-compliant, specific findings include;

A. The circuit breaker and panelboard supplying normal power to fire alarm control panel is not identified on control panel.

LIFE SAFETY CODE STANDARD

Tag No.: K0147

Based on observation, on February 7, 2012 at approximately 3:00pm onward, the following items were non-compliant, specific findings include;

A. There is a broken light switch located on basement level corridor wall near female staff room on security corridor.

B. There is no bonding jumper between normal and emergency panelboards serving the same patient vicinity. Panelboards are located in electrical room " E " of the northeast tower.