Tag No.: K0062

Based on observation it was determined the facility failed to maintain all sprinkler heads.

The findings included:

Observation of the kitchen on 5/28/13 at 12:30 P.M. revealed 2 of 2 brass coated sprinkler heads in the dishwashing room corroded and had a buildup of lint.

No Description Available

Tag No.: K0067

Based of observation, it was determined that the facility failed to provide exhaust in all soiled utility rooms.

The findings included:

Observation of the 4th floor on 5/28/13 at 10:00 A.M. revealed the soiled utility room did not have a means to exhaust air.

No Description Available

Tag No.: K0104

Based on observation, the facility failed to maintain fire walls.

The findings included:

1. Observation of the 4th floor on 5/28/13 at 10:20 A.M. revealed penetrations in the 2 hour fire separation across from the telemetry doors. The maintenance department sealed the penetrations on both sides of the wall immediately.