Tag No.: K0054
On the day of the recertification survey, based on review of records and interview with facility staff, from 9:00 a.m. until 1:00 p.m., the facility failed to ensure that the smoke detectors were being maintained in accordance with code.
Findings include:
There was no documentation showing the sensitivity test for the smoke detectors.
Tag No.: K0062
On the day of the recertification survey, based on review of records and interview with facility staff, from 9:00 a.m. until 1:00 p.m., the facility failed to ensure that the automatic sprinkler system was being maintained in accordance with code.
Findings include:
There was no documentation for the quarterly waterflow alarm test.