Bringing transparency to federal inspections
Tag No.: K0324
Based on record review and staff interview, the facility failed to conduct a monthly visual inspection for components of the kitchen exhaust hood fire-extinguishing system.  This condition did not ensure that all system components were in position and intact, that the system was not obstructed or damaged, and increased the potential that the suppression system would not operate as designed during a cooking fire.  
Findings are:
Record review on 4/10/19, at 11:20 am revealed documentation was not provided to verify that monthly visual kitchen exhaust hood fire-extinguishing system inspections were conducted by the facility.
In an interview on 4/10/19, at 11:20 am, Maintenance A confirmed the inspections were not documented.
Cooking equipment is protected in accordance with NFPA 96, Standard for Ventilation Control and Fire Protection of Commercial Cooking Operations.
NFPA 96, 2011, 10.2.6 Automatic fire-extinguishing systems shall be installed in
accordance with the terms of their listing, the manufacturer's
instructions, and the following standards where applicable:
(1) NFPA 12
(2) NFPA 13
(3) NFPA 17
(4) NFPA 17A 
NFPA 17A, 2009, 7.2 Owner ' s Inspection.
7.2.1 On a monthly basis, inspection shall be conducted in
accordance with the manufacturer ' s listed installation and
maintenance manual or the owner ' s manual.
7.2.2 At a minimum, this  " quick check "  or inspection shall
include verification of the following:
(1) The extinguishing system is in its proper location.
(2) The manual actuators are unobstructed.
(3) The tamper indicators and seals are intact.
(4) The maintenance tag or certificate is in place.
(5) No obvious physical damage or condition exists that
might prevent operation.
(6) The pressure gauge(s), if provided, shall be inspected
physically or electronically to ensure it is in the operable
range.
(7) The nozzle blowoff caps, where provided, are intact and
undamaged.
(8) Neither the protected equipment nor the hazard has not
been replaced, modified, or relocated.
Tag No.: K0761
Based on record review and staff interview, the facility failed to inspect and test fire rated doors annually throughout the facility.  This condition would allow the spread of fire through faulty fire rated doors that would otherwise contain a fire.
Findings are:
Record review on 4/10/19, at 11:25 am revealed a preventative maintenance plan to inspect and test fire rated doors annually was not provided for review.  
    
In an interview on 4/10/19, at 11:25 am, Maintenance A confirmed the fire door testing was not implemented. 
NFPA 80, 2010, 5.2* Inspections.
5.2.1* Fire door assemblies shall be inspected and tested not
less than annually, and a written record of the inspection shall
be signed and kept for inspection by the AHJ.
5.2.4 Swinging Doors with Builders Hardware or Fire Door
Hardware.
5.2.4.1 Fire door assemblies shall be visually inspected from
both sides to assess the overall condition of door assembly.
5.2.4.2 As a minimum, the following items shall be verified:
(1) No open holes or breaks exist in surfaces of either the
door or frame.
(2) Glazing, vision light frames, and glazing beads are intact
and securely fastened in place, if so equipped.
(3) The door, frame, hinges, hardware, and noncombustible
threshold are secured, aligned, and in working order
with no visible signs of damage.
(4) No parts are missing or broken.
(5) Door clearances do not exceed clearances listed in 4.8.4
and 6.3.1.7.
(6) The self-closing device is operational; that is, the active
door completely closes when operated from the full
open position.
(7) If a coordinator is installed, the inactive leaf closes before
the active leaf.
(8) Latching hardware operates and secures the door when
it is in the closed position.
(9) Auxiliary hardware items that interfere or prohibit operation
are not installed on the door or frame.
(10) No field modifications to the door assembly have been
performed that void the label.
(11) Gasketing and edge seals, where required, are inspected
to verify their presence and integrity.