Sprinkler System - Maintenance and Testing

Tag No.: K0353

Based on observation and interview, it was determined the facility failed to maintain the automatic sprinkler system in two instances, affecting two of fifteen smoke compartments.

Findings include:

1. Observation on April 1, 2025, revealed the following automatic sprinkler system deficiencies:

a) 9:30 a.m., there was a gap greater than 1/8 inch in the ceiling tile surrounding a dryer exhaust line in Room 503, which could affect operation of the automatic sprinkler system;
b) 9:47 a.m., there was a gap greater than 1/8 inch in the ceiling tile surrounding a dryer exhaust line in Room 433.


Interview with the Director of Facilities and Facilities Coordinator on April 1, 2025, at 2:00 p.m., confirmed the automatic sprinkler system deficiencies.

Corridor - Doors

Tag No.: K0363

Based on observation and interview, it was determined the facility failed to maintain corridor doors in one instance, for one out of over 30 doors tested.

Findings include:

1. Observation on April 1, 2025, at 9:15 a.m., revealed the door to resident room 505 failed to latch when tested.

Interview with the Director of Facilities and Facilities Coordinator on April 1, 2025, at 2:00 p.m., confirmed the corridor door deficiency.