Bringing transparency to federal inspections
Tag No.: K0321
K321 Hazardous Areas - Enclosure 2012 EXISTING
Findings:
The inspector observed, while accompanied by the Director Engineering and Quality Manager Quality Resources, during the hours of the inspection from 3:30 PM to 6:30 PM on 08/16/17 and the following day on 8/17/17 from 8:30 AM - 5:00 PM, accompanied by Director Engineering, Quality Manager Quality Resources, Facility Safety Manager, Maintenance Supervisor, and Mechanics, that there were the following issues:
1) Main Building, 4th floor. The door to the pharmacy storage room did not latch.
2) Main Building, 4th floor. In the Echo Testing patient care areas, the med surg rooms were used as either equipment storage or general storage. Hazardous areas are protected in accordance with NFPA 99, 2012, 19.3.2.1.
Tag No.: K0355
K355 Portable Fire Extinguishers
Findings:
The inspector observed, while accompanied by the Director Engineering and Quality Manager Quality Resources, during the hours of the inspection from 3:30 PM to 6:30 PM on 08/16/17 and the following day on 8/17/17 from 8:30 AM - 5:00 PM, accompanied by Director Engineering, Quality Manager Quality Resources, Facility Safety Manager, Maintenance Supervisor, and Mechanics, that there were the following issues:
1) The fire extinguishers log showed there were water extinguishers in use but field verification did not find any. Please update the inventory to match actual items in use.
Tag No.: K0902
K902 Gas and Vacuum Piped Systems - Other
Findings:
The inspector observed, while accompanied by the Director Engineering and Quality Manager Quality Resources, during the hours of the inspection from 3:30 PM to 6:30 PM on 08/16/17 and the following day on 8/17/17 from 8:30 AM - 5:00 PM, accompanied by Director Engineering, Quality Manager Quality Resources, Facility Safety Manager, Maintenance Supervisor, and Mechanics, that there were the following issues:
1) St. John's Campus. In the basement mechanical room, copper piping was not separated or insulated from dissimilar metal piping and supports to prevent bimetallic electrolyte action.
Tag No.: K0909
K909 Gas and Vacuum Piped Systems - Information and Warning Signs
Findings:
The inspector observed, while accompanied by the Director Engineering and Quality Manager Quality Resources, during the hours of the inspection from 3:30 PM to 6:30 PM on 08/16/17 and the following day on 8/17/17 from 8:30 AM - 5:00 PM, accompanied by Director Engineering, Quality Manager Quality Resources, Facility Safety Manager, Maintenance Supervisor, and Mechanics, that there were the following issues:
1) Main Building, 4th floor. At the cross corridor door near the stairs, above the ceiling, there were medical gas piped system piping without any label.
Tag No.: K0911
K911 Electrical Systems - Critical Branch
Findings:
The inspector observed, while accompanied by the Director Engineering and Quality Manager Quality Resources, during the hours of the inspection from 3:30 PM to 6:30 PM on 08/16/17 and the following day on 8/17/17 from 8:30 AM - 5:00 PM, accompanied by Director Engineering, Quality Manager Quality Resources, Facility Safety Manager, Maintenance Supervisor, and Mechanics, that there were the following issues:
1) There were circuits that were not items listed as allowed per NFPA 70 517.33 placed on the critical branch. This was exemplified by but not limited to: Main Building, 1st floor, critical panels "CHA", "CL1", and "SA".
2) There were circuits essential to the Life Safety Branch that were placed on the Critical Branch. This was exemplified by but not limited to: Main Building, 4th floor, critical panel "CL6"; Main Building, 5th floor, critical panel "CL8".
Tag No.: K0918
K918 Electrical Systems - Essential Electric System Maintenance and Testing
Findings:
The inspector observed, while accompanied by the Director Engineering and Quality Manager Quality Resources, during the hours of the inspection from 3:30 PM to 6:30 PM on 08/16/17 and the following day on 8/17/17 from 8:30 AM - 5:00 PM, accompanied by Director Engineering, Quality Manager Quality Resources, Facility Safety Manager, Maintenance Supervisor, and Mechanics, that there were the following issues:
1) There were no written records of maintenance and testing of the generators(s), performed by a third party company available for the year 2016.