HospitalInspections.org

Bringing transparency to federal inspections

2401 W MAIN

HENRYETTA, OK 74437

No Description Available

Tag No.: K0017

Based on interview and observation with staff, the facility failed to provide corridors separated from use areas by walls constructed with at least 1/2 hour fire resistance rating per 19.3.6.2.1. Findings:

1) Exit corridors were found
(a) to have unrated penetrations through rated corridor walls, including around wiring and conduit;
(b) to have outside vertical corners at rated wall intersections (above ceiling) with open gypsum board joints (no tape/bedding).

No Description Available

Tag No.: K0018

Based on observation and interview with staff, the facility failed to provide corridor doors with a means suitable for keeping the door closed. Findings:

1) Soiled Utility, located across from the nurse station, has doors that do not have latching hardware as required in 19.3.6.3.2.

No Description Available

Tag No.: K0022

Based on observation and interview with staff, the facility failed to provide all exits marked by approved, readily visible signs. Findings:

1) There were no exit signs in the Dining Room at the door leading into the exit corridor and at the door leading to the exterior.

No Description Available

Tag No.: K0025

Based on observation and interview with staff, the facility failed to provide smoke barriers of at least one-half hour fire resistance rating in accordance with Section 8.3. Findings:

1) Open penetrations were found in the smoke barriers, including around wiring, conduit, and structural members passing through the smoke barrier.

No Description Available

Tag No.: K0077

Based on observation and interview with staff, the facility failed to provide a piped in medical gas system complying with NFPA 99. Findings:

1) An Emergency Oxygen Supply Connection for connecting a temporary auxiliary source of supply for emergency or maintenance situations was not found Refer to NFPA 99 - 1999 Edition, Section 4-3.1.1.8(h).

2) No documentation was found re-certifying the medical gas system after the nitrous manifold was replaced in the medical gas room on 6-24-11. Refer to 4-3.4.1.

3) Medical gas copper piping was found to be in direct contact with galvanized supports (no isolation of dissimilar materials) in several locations in the facility.

No Description Available

Tag No.: K0144

Based on observation and interview with staff, the facility failed to provide documentation of inspection. Finding:
1) There is no documentation of an annual inspection and testing of the generator. Refer to NFPA 110 Section 8.4.