Tag No.: K0029

.

Based on observation and interview, the facility failed to ensure that there were no unsealed penetrations at all rated walls, as required by NFPA 101, 2003: 8.3.5.1.

Observations during the afternoon of 06/29/16, revealed there were unsealed holes and penetrations above the ceiling in the fire rated walls of the Soiled Linen Room on each level.

In an interview during the morning of 06/29/16, the Facility Engineer stated that the holes and penetrations would be properly sealed to achieve the required fire rating and that the entire facility would be checked.

.