Tag No.: K0056
On observation and interview with Staff M around 2:45pm, found storage closet #342 in hallway at Building 3 without a sprinkler head. This closet needs sprinkler protection to comply with CMS Regulations . NFPA 13 Standard for Sprinkler systems. 19.1.6
Tag No.: K0062
On observation and interview with Staff M around 2:00pm, found bushes obstructing the Fire Department Connection, BLD # 11, from being accessible for hoselines. These bushes need to be removed to allow the Fire Department to hook to the Fire department connection and pump into the sprinkler system. NFPA 25, 9.7.5