Tag No.: K0226
Based on observation and staff interview, the facility failed to ensure a set of doors in a horizontal exit would resist the spread of fire. This condition would allow the spread of fire between 2-hour separated areas of the facility.
Findings are:
Observation on 8/22/19, at 11:09 am revealed the 90-minute fire rated Double Doors 225 and 226 in the horizontal exit did not positively latch when self-closed.
In an interview on 8/22/19, at 11:09 am, Maintenance A confirmed the doors did not positively latch.
Tag No.: K0321
Based on observation and staff interview, the facility failed to separate hazardous areas with smoke resistive doors. This condition would allow smoke to enter the egress corridor.
Findings are:
Observation on 8/22/19, from 10:57 am to 11:48 am revealed:
1. The Linen Closet Storage Room Door did not positively latch when self-closed.
2. The Elevator Equipment Room Door did not positively latch when self-closed.
3. The Film Storage Room Door did not positively latch when self-closed.
4. OR Clean Closet Doors did not positively latch when self-closed.
In an interview on 8/22/19, from 10:57 am to 11:48 am, Maintenance A acknowledged the doors did not positively latch.
Tag No.: K0919
Based on observation and staff interview, the facility failed to use electrical wiring in a way that would not create a fire hazard. This condition had the potential to cause a fire.
Findings are:
Observation on 8/22/19, at 11:26 am revealed exposed electrical wiring was not installed in a junction box with a cover above the south interior door in the Main Electrical Room.
In an interview on 8/22/19, at 11:26 am, Maintenance A acknowledged the lack of junction box cover.
NFPA 70, 2011, 322.56 Splices and Taps.
(A) Splices. Splices shall be made in listed junction boxes.