HospitalInspections.org

Bringing transparency to federal inspections

12 THIRD STREET SE

HILLSBORO, ND 58045

Cooking Facilities

Tag No.: K0324

The facility failed to install cooking equipment in accordance with NFPA 96, Standard for Ventilation Control and Fire Protection of Commercial Cooking Operations.

A readily accessible means for manual activation shall be located between 1067 mm and 1219 mm (42 in. and 48 in.) above the floor, be accessible in the event of a fire, be located in a path of egress, and clearly identify the hazard protected. 19.3.2.5.1, 9.2.3, NFPA 96 10.5.1.

Observation determined the manual actuation devices for the fire-extinguishing systems serving the Main Kitchen exhaust hood, and the Swing Bed Dining Room exhaust hood, were mounted at a height of more than forty-eight (48) inches above the floor.

Failure to inspect, maintain, and install the wet chemical extinguishing system in accordance with NFPA 96 increases the risk of injury or death due to fire.

This deficiency affected two (2) of two (2) wet chemical extinguishing systems in the facility.

Smoke Detection

Tag No.: K0347

In spaces served by air-handling systems, detectors shall not be located where airflow prevents operation of the detectors. Detectors should not be located in a direct airflow or closer than 36 in. from an air supply diffuser or return air opening. 19.3.4.5.1, 9.6.2.10.1.1, NFPA 72 17.7.4.1, A.17.7.4.1

The facility failed to ensure the smoke detection system was in compliance with NFPA 72, National Fire Alarm and Signaling Code.

Observation determined one (1) smoke detector in the Therapy Room was installed within 36 in. of a ceiling fan.

Failure to install the smoke detection system as required increases the risk of death or injury due to fire.

This deficiency affected one (1) of numerous smoke detectors in the facility. The smoke detection system serves the entire facility.