107 SWIFT STREET

REFUGIO, TX 78377

No Description Available

Tag No.: K0011

This STANDARD is not met as evidenced by: Based on observations during the survey of the facility, on the morning of 06/06/2014, the construction of the required 2-hour rated common wall between the hospital and the physical therapy wing was not completed (in an area above ceiling on the physical therapy wing side of communicating opening/doors).

No Description Available

Tag No.: K0029

This STANDARD is not met as evidenced by: Based on observations during the survey of the facility, on the morning of 06/06/2014, a 3rd floor Soiled Linen room did not have the required 3/4 hour rated door, with self-closing device (closer). Also, the Laundry, located in the basement, did not have the required 3/4 hour rated door, with self-closing device (closer).