Bringing transparency to federal inspections
Tag No.: K0052
A fire alarm system required for life safety shall be, tested, and maintained in accordance with NFPA 70 National Electric Code and NFPA 72 National Fire Alarm Code and records kept readily available. The system shall have an approved maintenance and testing program complying with applicable requirement of NFPA 70 and 72. 9.6.1.4, 9.6.1.7,.
FINDINGS INCLUDE:
On facility tour between 8:00 AM and 2:00 PM on 03/09/2015, observation revealed that:
There was no automatic smoke detector with sounder base present in the M.D. Resident Sleeping Room (A341).
This deficient practice was confirmed by the Director of Maintenance upon discovery.
Tag No.: K0076
Medical gas storage and administration areas shall be protected in accordance with NFPA 99, Standard for Health Care Facilities.
(a) Oxygen storage locations of greater than 3,000 cu.ft. are enclosed by a one-hour separation.
(b) Locations for supply systems of greater than 3,000 cu.ft. are vented to the outside.
4-3.1.1.2 (NFPA 99), 8-3.1.11.1 (NFPA 99), 18.3.2.4, 19.3.2.4
FINDINGS INCLUDE:
On facility tour between 8:00 AM and 2:00 PM on 03/09/2015, observation revealed that:
4 oxygen cylinders were observed in an upright position unsecured by chain or other securing device in the oxygen storage room in the Home-OPBH Office/Clinic.
This deficient practice was confirmed by the Director of Maintenance upon discovery.