Tag No.: K0012
The facility failed to ensure the construction type of the Wishek Hospital meets the required building construction in Chapter 19.
During the revisit, observation determined the one-hour fire rated ceilings had multiple unsealed spaces.
Tag No.: K0017
The facility failed to provide corridors that were separated from use areas by walls with at least ? hour fire resistance rating.
During the revisit, observation determined the basement and first floor corridor walls had multiple through-wall pipe, data cable, conduit, and duct penetrations that were not sealed with fire rated material installed according to the manufacturer's instructions.