Bringing transparency to federal inspections
Tag No.: K0069
Based on observations it was determined that the health care facility failed to maintain the build up of grease in the kitchen on the cook line. This has the possibility to affect 30% of the residents.
The Findings Include:
On 10/27/2011 at approximately 1535 hours, it was revealed by observation and interview that there was excessive grease build up on the cook line in the kitchen; specifically in the hood catch pan and on the floor behind the line.
On 10/27/2011 at approximately 1550 hours, it was revealed by observation and interview that there was excessive grease build up behind the grill and fryer on the serving line.
An interview on 10/27/2011 at approximately 1550 hours, with maintenance personnel confirmed this evidence.
Tag No.: K0147
Based on observations it was determined that the health care facility failed to maintain the proper use of extension cords and power strips. This has the possibility to affect 15% of the residents.
The Findings Include:
On 10/27/2011 at approximately 1035 hours, it was revealed by observation and interview that there were daisy chained power strips in the 5th floor nursing supervisor's office.
On 10/27/2011 at approximately 1335 hours, it was revealed by observation and interview that there was an extension cord in use in the quality services office.
An interview on 10/27/2011 at approximately 1335 hours, with maintenance personnel confirmed this evidence.