Bringing transparency to federal inspections
Tag No.: K0130
OTHER DEFICIENCY NOT ON 2786
This STANDARD is not met as evidenced by:
A. Due to the number, variety, and severity of the life safety deficiencies observed during the
survey walk-through, the provider shall institute the appropriate Interim Life Safety Measures
until all cited deficiencies are corrected. The provider shall include, as an attachment to its Plan
of Correction (PoC) and referenced therein, a detailed narrative and proposed schedule for all
such measures. The narrative shall describe all measures to be implemented, as well as the frequency with which they are to be conducted, and shall indicate the manner in which the measures are to be documented. The narrative shall also include comments related to changes in the Interim Life Safety Measures to remain in place as work toward the completion of its PoC progresses.
Tag No.: K0145
Based on random observation during the survey walk-through, accompanied by facility staff, and in staff interviews, the division of the emergency electrical system into life safety, critical, and equipment branches as required by NFPA 99 1999 could not be verified.
Findings include:
A. In the morning of 08/26/2014, in the electrical room, the locations of the life safety, critical branch, and equipment electrical panels were not known to the staff accompanying the surveyor so the load distribution and division of the circuiting could not be verified. NFPA 99 1999 3-4.2.2.2